257662 / 856860300010
2022‐10‐10·BA00·III·en·01
Annex A
13
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Moulded case circuit breaker (MCCB)
Series 8568
13
Annex A
13.1 Technical Data
Explosion Protection
Global (IECEx)
Gas
IECEx FMG 16.00005X
Ex db eb IIC T6 to T4 Gb
Europe (ATEX)
Gas
FM 16 ATEX 0005X
E
II 2 G Ex db eb IIC T6 to T4 Gb
Certifications and certificates
Certificates
IECEx, ATEX, USA, Canada
Technical Data
Versions
8568/MCCB-GS101B-...A
8568/MCCB-GS102B-...A
Electrical data
No. of poles
1-pole
2-pole
Temperature classes -30 °C
(
T
amb
(
+40 °C
15 to 60 A: T6
70 to 125 A: T5
-30 °C
(
T
amb
(
+60 °C
T4
Temperature-
resistant conductors
IECEx / ATEX:
-30 °C
(
T
amb
(
+40 °C
15 to 60 A: 75 °C
70 to 125 A: 90 °C
-30 °C
(
T
amb
(
+60 °C
110 °C
NEC:
-30 °C
(
T
amb
(
+60 °C
15 to 125 A: 90 °C
Rated operational
voltage U
e
IECEx / ATEX:
AC: 240 V
DC: 125 V
NEC:
AC: 347 V
DC: 125 V
IECEx / ATEX:
AC: 240/415 V
DC: 125/250 V (2 poles in series)
NEC:
AC: 480
DC: 125/250 V (2 poles in series)
Rated insulation
voltage U
i
630 V
Rated impulse
withstand voltage
U
imp
6 kV
Summary of Contents for 8568/MCCB-GS10.B-100A