english
Operating Instructions
Digital Output Loop Powered Type 9176
19
6
Cabinet installation
The ISpac isolators can be used over a wide temperature range. Depending on the isolator
version and installation method may result in different maximum ambient temperatures.
!
Warning
Follow the instructions of the “ISpac cabinet installation guideline”
Device may fail because of high ambient temperature.
The manufacturer’s liability and warranty expire.
o
The cabinet need to be built in a way which allows to operate the device within the
specified temperature range
The cabinet installation guide is available on
7 Transport and storage
-
Transport and store the device only within the original packaging
-
Store the device dry and without vibrations.
-
Do not drop the device.
8 Arrangement and fitting
8.1 Dimensions
8.2 Installation
The digital outputs may be installed in Zone 2, Zone 22 or outside hazardous areas.
In the case of operation in Zone 2 or Zone 22 the digital outputs must be fitted in an
enclosure which complies with the requirements of IEC/EN 60079-15 or IEC/EN 60079-31.
Size X
Screw terminals
108 mm
Spring clamp terminals 128 mm