Fieldbus Isolating Repeater
Type 9185/1*-**-10
FM
1 of 1
none
91 856 01 31 1
Einsiedler
04.05.
2007
Reistle
24.08.11
01
F. Danko
02
22.10.12
Reistle
28.02.14
Reistle
03
Type 9185/11-**-10
Hazardous area
Safe area
The Fieldbus Isolating Repeater Type 9185/11-**-10 is an
associated apparatus as well as a nonincendive apparatus
for installation in Non-Hazardous, Class I, Division 2 or
Zone
2
Hazardous
(Classified)
Locations
providing
intrinsically safe connections for one field device located in
Class I, II, III, Division 1, Group A-G or Class I, Zone 1 [AEx
ib] Group IIC, Hazardous Locations according to NEC
Article 504/505 as listed below.
Type 9185/12-4*-10
Safe area
The Fieldbus Isolating Repeater Type 9185/12-4*-10 is a
nonincendive apparatus located in Non-Hazardous or Class
I, Division 2 or Zone 2 Hazardous Location.
Hazardous area:
Class I, II, III; DIV 1; Group A-G or Class I; Zone 1; Group IIC/IIB Hazardous Locations
Safe area:
Non-Hazardous; Division 2 or Zone 2 Hazardous (Classified) Locations
Fieldbus Isolating Repeater Type 9185/1b-cd-10
b = numeral 1 or 2 for I.S. or non I.S. field interface
c = numeral 3 or 4 for type of field interface
d = numeral 5 or 6 for functionality
Entity parameters for wiring configurations are as follows:
L
o
L
o
C
o
C
o
Type
V
OC
[V]
I
SC
[mA]
P
O
[mW]
CL I, DIV 1, A,B/
Zone 1, GP IIC
CL I, DIV 1, C-G/
Zone 1, GP IIB
CL I, DIV 1, A,B/
Zone 1, GP IIC
CL I, DIV 1, C-G/
Zone 1, GP IIB
V
max
[V]
I
max
9185/11-35-10
9185/11-45-10
9185/11-46-10
3.73
5.88
5.88
149
50
50
139
73.3
73.3
1.3 mH
15 mH
15 mH
7 mH
56 mH
56mH
100 µF
43 µF
43 µF
1000 µF
1000 µF
1000 µF
± 4.2
± 5.88
± 5.88
-
-
-
Notes:
1.
Intrinsically safe apparatus may be switches, thermocouples, LEDs, RTDs or an FM Approved System or Entity
device connected in accordance with the manufacturer´s installation instructions.
2.
For Entity concept use the appropriate parameters to ensure the following:
V
t
or V
OC
V
max
C
o
, C
a
C
i
+ C
leads
P
o
P
i
I
t
or I
SC
I
max
L
o
, L
a
L
i
+ L
leads
3.
Electrical apparatus connected to an intrinsically safe system should not use or generate voltages > 250 V (U
max
).
4.
Installation should be in accordance with Article 504/505 of the National Electrical Code, ANSI/NFPA 70 and
ANSI/ISA RP 12.06.01.
5.
Installation in Canada should be in accordance with the Canadian Electrical Code, CSA C22.1, Part 1, Appendix F.
6.
Use a general purpose enclosure meeting the requirements of IEC 61010-1 for use in Non-Hazardous or Class I,
Division 2, Hazardous (Classified) Locations.
7.
Use an FM Approved Dust-ignition proof enclosure appropriate for environmental protection in Class II, Division 1,
Groups E, F and G; and Class III, Hazardous (Classified) Locations.
8.
These modules are to be mounted on DIN rail, DIN rail with pac-Bus (type 9194) or pac-Carrier (type 9195).
The field wiring in any case is connected to the ISpac device terminals.
9.
Ambient temperature:
-20°C … +70°C (any mounting position)
WARNING:
Do not disconnect equipment when a flammable or combustable atmosphere is present.
AVERTISSEMENT:
Ne pas débrancher l’équipement en présence d’atmosphère inflammable ou combustible.