CPU module for Zone 2
Series 9442/35
Diagnostic and
parameterisation
Functions
• Use the web server or IS1+ detect software to set the IP address
(for Ethernet)
• Web server
• Load or read back configuration data and parameters in the IS1+
field stations
• Read inputs
• Read and write outputs
• Transmit diagnostics data (e.g. configuration error, hardware error,
signal error)
• Transmit HART commands from/to HART field devices
• Firmware downloads using the web server
Retrievable
parameters
Manufacturer, type, hardware revision, software revision, serial number
Connectable
software packages
• IS Wizard (using the USB ServiceBus)
• R. STAHL DTM devices with FDT frames (e.g. FDT container by
M+M; PACTware)
• AMS by Emerson Process Management
• PDM by Siemens
• PRM and Fieldmate by Yokogawa
• FieldCare by E Hauser
• FDM by Honeywell
Galvanic separation
Test voltage
acc. to standard EN 60079-11
Between the
auxiliary power
and CPU
)
1500 V AC
Between 2
CPUs
(redundancy)
)
1500 V AC
Electromagnetic
compatibility
Tested to the following standards and regulations: EN 61326-1 (2013)
IEC 61000-4-1 to 61000-4-6, NAMUR NE 21
Ambient conditions
Ambient temperature -40 to +75 °C (observe operating instructions of the series 9496/35 base)
Storage temperature -40 to +80 °C
Maximum relative
humidity
95% (without condensation)
Maximum operating
height
< 2000 m
Semi-sinusoidal
shock
(IEC EN 60068-2-27)
15 g (3 shocks per axis and direction)
Sinusoidal vibration
(IEC EN 60068-2-6)
1 g in the frequency range 10 to 500 Hz
2 g in the frequency range 45 to 100 Hz
Technical Data