7.2
Mounting / dismounting, operating position
Suspension at fixed mounting points
The luminaire
• must be fastened with suitable screws
• must be mounted on a flat surface
7.3
Installation
7.3.1 Opening and Closing of the Enclosure
WARNING
Danger due to electrostatic discharge!
Explosion protection is impaired!
Do not install within arm's reach!
Ensure that no electrostatic charging may occur.
For example:
• due to accidental friction,
• by cleaning with a dry cloth,
• with particle streams.
For outdoor use, we recommend to install a 8162/1 breather from
R. STAHL Schaltgeräte GmbH.
The breather guarantees compliance with degree of protection IP64 in all
mounting positions.
WARNING
Danger due to inadmissible heating.
Explosion protection is impaired!
External heat sources and/or direct sunlight may effect the temperature class
and the maximum permissible surface temperature.
Early failure of equipment.
• The maximum ambient temperature must not be exceeded by external
heat sources.
The luminaire is suitable for wall and ceiling mounting.
Wet area, the mounting position with light emission upwards is not allowed.
DANGER
Risk of electric shock!
Risk of fatal injuries!
• Luminaires without switch must not be opened when they are supplied
with power (see information plate on the lock)!