Operation
Operating Instructions ET-xx6-A
R. STAHL HMI Systems GmbH / OI_ET_xx6_A_en_V_03_00_36.docx / 03.05.2021
Page 33 of 60
X8
0
+U_INT1
Reader interface
1
0V
I.S.
2
+U_EX1
3
GND
4
+U_RD
5
Signal 1
6
Signal 2
7
Signal 3
8
Signal 4
9
+U_EX1 (out)
X9
1
VCC
PS2 interface *
2
KBDAT
I.S.
3
KBCLK
for
4
MSDAT
external keyboard /
5
MSCLK
mouse
6
GND
X10
1
Optical fiber connection type duplex SC - female
Ethernet optical
fiber interface **
X11
1
TxD (+)
Ethernet copper
2
TxD (-)
Connection **
3
RxD (+)
4
RxD (-)
The COM interface
may only
be wired as a RS-232
or
as a
RS-422/485 connection !
Simultaneous wiring of the RS-232 and RS-422/485 interface is
not
allowed
!
* Do
NOT
connect the optional external keyboard to live equipment !
** Please note that the Ethernet connection is
either
for an optical
fibre connection (X10)
or
for a copper connection (X11), depending
on the version ordered !
The optical fiber connection requires a multimode optical fiber cable
with 62.5 µm core diameter and 125 µm external diameter.
Copper wires with cross sections of between 0.2 mm² (AWG24)
and 2.5 mm² (AWG14) may be connected to any of the terminals
of the HMI devices.
Which cable cross sections are chosen should be decided on the
basis of relevant regulations, such as DIN VDE 0298. Factors that
might require a larger cross section, such as current, increased
temperatures, cable bundling, etc. must also be taken into
account !
NOTICE