Technical data
Explosion Protection
Global (IECEx)
Gas and dust
IECEx IBE 14.0080X
EX nA d op is IIC T4 Gc
EX tb IIIC T100 °C Db
EX tc IIIC T100 °C Dc
Europe (ATEX)
Dust
IBExU14ATEX1292
E
II 2 D Ex tb IIIC T100 °C Db
Gas and dust
IBExU14ATEXB020 X
E
II 3 G Ex nA d op is IIC T4 Gc
E
II 3 D Ex tc IIIC T100 °C Dc
Certifications and certificates
Certificates
IECEx, ATEX
Technical Data
Electrical data
Ballast
AC: 220 ... 240 V ±10 %; 50 ... 60 Hz
DC: 200 ... 250 V ±10 %
Inrush current
I
peak
= 53.5 A; Δt = 124.8
m
s
maximum number of luminaires per miniature circuit breaker:
Power factor
)
0.93
Degree of protection IP66 / IP67 (IEC 60598)
Protection class
I (with internal PE connection)
Impact strength (IK
code)
IK10 (IEC 62262)
Disconnection of the
light
When opening the luminaire
Switch with safety lock (optional); when opening the central lock all poles of the
voltage supply to the ballast are disconnected; contacts of the switching ele
-
ment are positive opening, they can only be switched on again when the lumi
-
naire trough and the central locking system are closed.
Type
10 A
16 A
20 A
25 A
B
8
12
16
20
C
13
21
27