259910 / L40260300020
2017-09-18·BA00·III·en·00
Commissioning
17
Linear Luminaire with LED
Series EXLUX L402/2
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
7.3.3 Cable entries
The standard luminaire is delivered with 3 lead-in holes, 2 cable glands and 2 stopping
plug.
Please observe the tightening torque for luminaires with installed cable glands and
stopping plugs from R. STAHL Schaltgeräte GmbH.
Luminaires with cable glands and stopping plugs; not supplied by
R. STAHL Schaltgeräte GmbH
Please note:
• the required temperature resistance!
• the IP degree of protection according to the rating plate!
• the operating instructions of the cable glands and stopping plugs!
• the required tightening torques!
• the range of the permissible cable diameter!
8
Commissioning
Before commissioning, ensure that
• the device has been installed according to regulations.
• the power supply voltage and the rated operational voltage are identical.
• the required cable diameter for cable glands has been used.
• the cable entries and stopping plugs have been securely tightened.
• the cables are correctly connected.
• the connection has been performed correctly.
• all screws and nuts are tightened according to regulations.
• the connection chamber is clean.
• the device is not damaged.
• no foreign bodies are inside the device.
• the device is sealed according to regulations.
• the LED assembly and the diffusor are clean.
Tightening torque
Connection thread
Pressure screw
Cable gland 8161
M20 x 1.5
2.3 Nm
1.5 Nm
M25 x 1.5
3.0 Nm
2.0 Nm
Stopping plugs 8290
M20 x 1.5
1.0 Nm
M25 x 1.5
1.5 Nm
Summary of Contents for EXLUX L402/2 Series
Page 20: ......