Function and device design 

Operating Instructions ET-xx8 / MT-xx8

 

 R. STAHL HMI Systems GmbH / OI_ET_MT-xx8_en_V_01_02_03.docx / 10.03.2021 

Page 25 of 84 

 

4.5 

Operating elements 

4.5.1 

ET-/MT-x38 (15") 

 

 

 

4.5.2 

ET-/MT-x98 (21.5") 

 

 

 

4.6 

LED status display 

Pictogram 

LED colour 

Status 

Meaning 

 

  Blue 

lit 

For "outdoor installation" version: internal heater 
is switched on. The device is being heated up. 

 

  Orange 

lit 

Device is live. 
Internal power supply ok. 

 

  Green 

lit 

Internal temperature has reached the required 
operating temperature level. 
The device is ready. 

 
 

 

Item 

Designation 

LEDs and front camera (optional) 

Display (optional: with touch function) 

Function keys F1 to F8 

Item 

Designation 

LEDs and front camera (optional) 

Display (optional: with touch function) 

Function keys F1 to F8 

RFID card reader (optional) 

Summary of Contents for SHARK 400 Series

Page 1: ...8 MT xx8 Series 400 Panel PCs Series 500 Thin Clients Series 600 KVM Systems Doc no 20141870000 HW Rev ET MT 4x8 01 01 04 HW Rev ET MT 5x8 01 01 04 HW Rev ET MT 6x8 01 01 03 Operating Instructions Ver...

Page 2: ...2 ATEX IECEx MT xx8 10 1 5 3 3 EMC directive 2014 30 EU 10 1 5 3 4 Radio equipment directive 2014 53 EU 10 1 5 3 5 Low voltage directive 2014 35 EU 10 1 5 3 6 RoHS directive 2011 65 EU 11 1 5 3 7 FM U...

Page 3: ...SERIES 400 500 28 4 7 5 Type key code E box module SERIES 600 30 4 8 Approval label 31 4 8 1 Ex classification ATEX IECEx 31 4 8 2 Ex classification EAC 31 4 8 3 Ex classification FM USA 32 4 8 4 Ex...

Page 4: ...n 46 11 1 Operating the touch display 46 11 2 Switching the device on and off 47 11 2 1 Without optional on off switch 47 11 2 2 With optional on off switch for SERIES 400 and 500 only 47 11 3 Teaming...

Page 5: ...X21 FO 1 FO 2 type LX 61 18 5 4 X22 FO 3 type OSX 61 18 5 5 X22 FO 3 type OLX 61 18 6 Non intrinsically safe interfaces Ex e 62 18 6 1 X1 Power supply 62 18 6 2 X2 X3 copper1 copper2 62 18 6 3 X4 DC...

Page 6: ..._ET_MT xx8_en_V_01_02_03 docx 10 03 2021 23 1 Panel mount with xx8 Mounting Kit 73 23 2 Control Drawing FM USA Canada 74 24 Attachment H 77 24 1 Declarations of EC conformity 77 24 1 1 EU 77 24 1 1 1...

Page 7: ...rademarks and or products of the companies in question 1 2 2 Disclaimer All rights reserved This document may not be reproduced in whole or in part except with the written consent of the publisher Thi...

Page 8: ...ance staff at all times Pass the operating instructions on to each subsequent owner or user of the device Update the operating instructions every time R STAHL issues an amendment 1 3 3 Application Ope...

Page 9: ...ificate number CE ATEX Europe BVS 14 ATEX E 134 X IECEx Global BVS 14 0116X EAC Russia TC RU C DE ME92 B 00843 EAC N RU DEPA01 B 27604 20 NEC USA FM 16 US 0278 X CEC Canada FM 16 CA 0141 X CCC China 2...

Page 10: ...0079 5 2015 Protection by powder filling q IEC 60079 7 2015 Protection by increased safety e IEC 60079 11 2012 Protection by intrinsic safety i IEC 60079 15 2010 Type of protection n IEC 60079 28 2015...

Page 11: ...owder filling q ANSI UL 60079 7 2017 Protection by increased safety e ANSI ISA 60079 11 2014 Protection by intrinsic safety i ANSI ISA 60079 15 2013 Type of protection n ANSI ISA 60079 28 2013 Optical...

Page 12: ...1610 11 2014 IEC 60079 11 2011 Protection by intrinsic safety i 31610 15 2014 IEC 60079 15 2010 Type of protection n 60079 31 2010 Protected by enclosures t dust 31610 28 2012 IEC 60079 28 2006 Optica...

Page 13: ...ation or a web page 2 2 Warning notes Dangerous situation which can result in fatal or severe life changing injuries if the safety measures are not complied with Dangerous situation which can result i...

Page 14: ...according to ATEX directive Device marking according to EU directive 0158 ID number of monitoring body Marking according to WEEE directive 2012 19 EU Marking for device approval in Eurasian Economic...

Page 15: ...e certified for the following hazardous areas Series xx8 Hazardous area Directive ET Zone 1 2 21 and 22 EPL Gb Db Class I Zone 1 2 Class I Division 2 Zone 21 22 ATEX directive IEC and Canadian require...

Page 16: ...es complying with these Operating Instructions and the other applicable documents such as the data sheet All other uses are only considered to be intended after being approved by R STAHL 3 2 Predictab...

Page 17: ...lly safe circuits at terminals X36 and X37 are earthed When connecting external antennae please note the following earthing requirements for intrinsically safe circuits EN 60079 14 of the National Ele...

Page 18: ...ing and the device for damage Immediately report any damage to R STAHL Store the device ideally in its original packaging in a dry place with no condensation and make sure that it is stable and protec...

Page 19: ...arry voltages higher than 250 VAC 50 60 Hz Connect Ex i devices only to intrinsically safe terminals In hazardous areas always switch the electrical circuits and devices to a de energised state before...

Page 20: ...ty concept The key to a successful concept is integrated implementation continuous maintenance and state of the art technology This is the responsibility of the plant operator The following are key is...

Page 21: ...be operated in temperatures ranging from 10 C to 65 C outdoor option O0 standard For outdoor option O4 the devices will be fitted with an integrated heater allowing operating temperatures ranging from...

Page 22: ...tures depend on the technology see chapter 17 1 Technical data 4 1 6 Accessories Peripherals Barcode scanner Attached keyboard and pointing device trackball or joystick Ex ia Desktop keyboard with 105...

Page 23: ...Page 23 of 84 4 3 Dimensions 4 3 1 Front 4 3 2 Page VESA 200 Standard 4 3 3 Page VESA 200 Top Connect Dimensions mm Item ET x38 MT x38 ET x98 MT x98 A 380 553 B 394 458 Dimensions mm Item ET x38 MT x3...

Page 24: ...200 Standard Cable glands number size see ET MT xx8 Installation Manual IM_ET_MT xx8 4 4 2 VESA 200 Top Connect Screw plugs number size see ET MT xx8 Installation Manual IM_ET_MT xx8 Item Designation...

Page 25: ...ion version internal heater is switched on The device is being heated up Orange lit Device is live Internal power supply ok Green lit Internal temperature has reached the required operating temperatur...

Page 26: ...ice 4 7 1 Position 4 7 2 Design of a type label taking the field system type label as an example Item Designation 1 Type key code see chapters 4 7 3 to 4 7 5 2 Article number of hardware 3 QR code 4 M...

Page 27: ...hen Family set to 8 Display size code Hyphen Application range zone Position in type key Possible value Description xT ET Devices for Zone 1 Zone 21 EPL Gb Db MT Devices for Zone 2 Zone 22 EPL Gc Dc H...

Page 28: ...amera 4 7 4 Type key code E box module SERIES 400 500 xT xx8 xxXxCWxxxxX00 PxRxMxIxSxE0x0 Enclosure design operating system additional interfaces Data memory Main memory Processor Hyphen Option box Pl...

Page 29: ...TPM P5 Intel i5 processor P6 Intel i5 processor with TPM Rx R3 4 GB main memory R4 8 GB main memory R5 16 GB main memory Mx M5 60 GB memory M6 80 GB memory M9 128 GB memory MB 160 GB memory MC 240 GB...

Page 30: ...ype key Possible value Description xT ET Devices for Zone 1 Zone 21 EPL Gb Db MT Devices for Zone 2 Zone 22 EPL Gc Dc Hyphen xx 6x E box SERIES 600 8 8 Generation 8 Hyphen xxX 1TX 1x 100 1000Base TX C...

Page 31: ...ECEx according to IEC 60079 0 and ATEX directive 2014 34 EU ET xx8 HMI series Version 2014 34 EU prefix Ex marking Gas e II 2 1 G Ex eb q ia op is Ga IIC T4 Gb Dust e II 2 1 D Ex tb ia op is Da IIIC T...

Page 32: ...series Version Ex marking Gas Class I Zone 2 AEx nA nR ia op is Ga IIC T4 Gc Class I Div 2 Groups A B C D T4 Dust Zone 22 AEx tc ia op is Da IIIC T115 C Dc Class II Div 2 Groups F G T4 Class III 4 8...

Page 33: ...x e nR ia Ga IIC T4 Gc Dust Ex tD iaD A22 IP66 T115 C 4 8 6 Ex classification CNEX China Chinese Ex classification according to GB3836 x ET xx8 HMI series Version Ex marking Gas Ex eb q ia op is Ga II...

Page 34: ...0 years of security updates and new builds with feature updates only every 2 3 years with these being optional The LTSC versions are ideal for industrial applications and feature additional security c...

Page 35: ...rnal storage media 5 4 3 Switching off closing down The Microsoft Windows operating system stores key data in the main memory regardless of the application and has to store this data on the hard disk...

Page 36: ...I_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 5 5 License sticker The license sticker for the Windows 7 Ultimate operating system is located inside the E box terminal box The license sticker for the Windo...

Page 37: ...ransport to the haulier responsible and have it confirmed Transport and store the device in undamaged packaging ideally the original packaging Transport and store the device carefully and in accordanc...

Page 38: ...nd Zone 22 The site of installation must be stable and suitable for the dimensions of the device and able to bear the load of its weight and that of any necessary attachments Avoid touch screen contam...

Page 39: ...fixing frame is used to fix the device inside the cover cut out of the enclosure It is mounted from the back For a detailed description of the panel mount with xx8 Mounting Kit see chapter 23 1 Panel...

Page 40: ...e laser diode is assigned to the laser class 1M Do not view the laser radiation directly within a distance of 100 mm with optical instruments e g magnifiers microscopes Explosion hazard due to electro...

Page 41: ...1 Nm to 1 5 Nm 8 5 6 Connecting associated equipment The cover of the terminal boxes Ex i Ex e Ex nA includes mounting options for associated equipment such as cable glands cable connectors buttons T...

Page 42: ...must be approved for the following areas or higher o Certified zone o Permitted temperature range o Country approval e g ATEX for Europe of the device Alternative similar and certified cable glands ma...

Page 43: ...s The plug connectors are designed to be readily connected or disconnected without load Tighten the plug connector screws Ensure that the following maximum rated current values are not exceeded o The...

Page 44: ...s area X33 Ex i x x e g KBDi USB xx8 keyboard cable X34 Ex i x x e g KBDi USB xx8 pointing device cable X35 Ex i x x e g USBi drive X6 Ex e any USB device explosion protected but non intrinsically saf...

Page 45: ...terminals o Existing screw connections 2 Switch on power supply o The device will start up in its standard configuration 3 Follow the instructions on the screen 10 Re Commissioning 1 Check the device...

Page 46: ...s displayed permanently 11 1 Operating the touch display Touching the touch screen with pointed or sharp items Non compliance may result in damage to the touch display shorter life span or total break...

Page 47: ...efined via the operating system and functions like a notebook switch For SERIES 400 and 500 devices R STAHL recommends you switch off the devices via the respective Windows Remote Image function 11 3...

Page 48: ...e power supply o Isolate supply and all Ex e circuits and wait 5 minutes before opening the terminal boxes Hot surfaces Non compliance may result in minor burns In ambient temperatures exceeding 45 C...

Page 49: ...lified staff only see chapter 3 3 Personnel qualification 12 4 1 Mounting dismounting the modules The xx8 SERIES HMIs consist of a display and an E Box module which are mounted together These modules...

Page 50: ...end the device with the RMA ticket included in the package to R STAHL HMI Systems GmbH see chapter 1 1 Manufacturer for the address 14 Cleaning Check the device for damage before and after cleaning it...

Page 51: ...ltage range AC 100 240 V DC rated operational voltage 24 V Voltage range DC 20 30 V Power consumption AC 1 0 6 A at 230 VAC 0 8 A with heater Power consumption AC 2 1 1 A at 110 VAC 1 7 A with heater...

Page 52: ...controller AMT is supported from operating system Open HMI Win10 IoT Enterprise 1607 64 bit Rev 1 4 3 onwards Image Remote HMI V5 70 xx 64 bit Touchscreen activation No activation pressure required T...

Page 53: ...ible Depending on how low the temperature is this process may last up to 3 hours Devices with AMD processor cannot be warm started in temperatures above 55 C 17 1 5 Mounting Function Equipment ET 438...

Page 54: ...Processor details AMD 2 2 GHz Dual Core 10W TDP Intel i7 1 7 GHz Dual Core 4 threads 3 Generation Ivy Bridge 17W TDP Intel i5 1 9 GHz 2 7 GHz Quad Core 4 threads 6 MB Cache 25W TDP Graphics controller...

Page 55: ...and use of 9721 13 11 14 Interface medium multi mode optical fibre cable USB interface 3x USB Ex ia 1x USB Ex e Serial interface 1x RS 232 RS 422 RS 485 Ex e Optional interface 1 WLAN 2 4 GHz Ex i WLA...

Page 56: ...al cable USB interface 3x USB Ex ia 1x USB Ex e Serial interface 1x RS 232 RS 422 RS 485 Ex e Audio interface 1x Audio line out Ex e Interface reader 1x reader barcode reader interface Ex i Front came...

Page 57: ...0 00 ET xx8 MT xx8 Certification status 2014 10 06 01 00 01 2014 11 14 01 01 00 ET xx8 MT xx8 Certificate 1 Supplement 2017 04 28 01 01 00 2017 05 29 01 01 01 ET xx8 MT xx8 Modification module C5 and...

Page 58: ...ezoidal output characteristics Max external capacitance Co 65 10 F Max external inductance Lo 1 20 H Co and Lo pairs directly above underneath each other may be used 18 2 2 X31 Fan X31 Fan power X31 1...

Page 59: ...airs directly above underneath each other may be used X32 Barcode card reader data line TXD X32 3 RXD X32 4 per circuit GND X32 5 Max output voltage Uo between RxD and GND or TxD and GND 5 35 VDC betw...

Page 60: ...ax external inductance Lo 0 68 1 68 2 68 3 68 4 68 H Co and Lo pairs directly above underneath each other may be used 18 2 6 X36 X37 RF1 RF2 X36 X37 RF1 RF2 Typ W02 W05 W22 W55 W25 per circuit Radio f...

Page 61: ...Max RF threshold power Po 33 2 dBm W 18 5 Inherently safe optical interfaces Ex op is 18 5 1 X20 X21 FO 1 FO 2 type FX Wavelength 1310 nm Nominal optical radiated power 0 344 mW Max optical radiated p...

Page 62: ...Hz 18 6 2 X2 X3 copper1 copper2 Nominal voltage 5 VAC VDC Max input voltage Um 250 VAC 18 6 3 X4 DC out Nominal voltage terminal 1 12 VDC Nominal voltage terminal 4 24 VDC Max input voltage Um 250 VA...

Page 63: ...Blue 5 PE earth Green yellow 6 PE earth Green yellow X2 1000Base TX 100Base TX Data cable CAT1 1 D1 TX Orange White Copper connection 1 2 D1 TX Orange 3 D2 RX Green White 4 D2 RX Green 5 D3 White Blue...

Page 64: ...ve one Ethernet connection Although SERIES 600 devices have the X3 terminal block CAT2 this is not assigned connected Terminal Pin Designation PCB view typical colour coding plug type Connection funct...

Page 65: ...inals Terminal Pin Designation PCB view typical colour coding plug type Connection function X30 PB 1 PB on off switch connection not possible for SERIES 600 2 GND 3 GND 4 GND X31 FAN 1 FAN Fan connect...

Page 66: ...R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 X36 SMA reverse socket WLAN Antenna connection 1 not possible for SERIES 600 for 2 4 GHz antenna X37 SMA reverse socket WLAN Antenn...

Page 67: ...the device from direct sunlight Wind may cool down the device and thus have an impact on the minimum operating temperature The storage temperature is not impacted by the type of installation As a rul...

Page 68: ...Inclination Description Highest permissible ambient temperature Portrait vertical 90 standing free HTC 60 C HTF 140 F Portrait vertical 45 standing free HTC 60 C HTF 140 F Landscape horizontal install...

Page 69: ...and Conditions 21 1 1 Declaration of substances and restricted substances The present declaration is based on the procedure described in the international standard and directives as listed in the tabl...

Page 70: ...ROHS directive 2011 65 EC The devices meet the requirements of RoHS Directive 2011 65 EU 21 1 1 3 IMO Resolution MEPC 269 68 The devices meet the requirements of the MEPC 269 68 Resolution of the Int...

Page 71: ...n the display consisting of 3 sub pixels in the basic colours red green and blue R G B Dot Sub pixel in the basic colour red green or blue or or Bright Sub pixel dot to which light is passing through...

Page 72: ...ective pixels bright dots 3 2 2 dark dots 3 3 5 total number of dots 5 3 5 adjacent dots 2 bright dots 1 pair 0 pair 1 pair more than 3 bright dots not acceptable 2 dark dots 1 pair 1 pair 2 pairs mor...

Page 73: ...Appendix G Operating Instructions ET xx8 MT xx8 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 Page 73 of 84 23 Appendix G 23 1 Panel mount with xx8 Mounting Kit...

Page 74: ...Operating Instructions ET xx8 MT xx8 Appendix G Page 74 of 84 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 23 2 Control Drawing FM USA Canada...

Page 75: ...Appendix G Operating Instructions ET xx8 MT xx8 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 Page 75 of 84...

Page 76: ...Operating Instructions ET xx8 MT xx8 Appendix G Page 76 of 84 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021...

Page 77: ...chment H Operating Instructions ET xx8 MT xx8 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 Page 77 of 84 24 Attachment H 24 1 Declarations of EC conformity 24 1 1 EU 24 1 1 1 ET...

Page 78: ...Operating Instructions ET xx8 MT xx8 Attachment H Page 78 of 84 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 24 1 1 2 MT xx8...

Page 79: ...Attachment H Operating Instructions ET xx8 MT xx8 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 Page 79 of 84 24 1 2 RCM...

Page 80: ...Operating Instructions ET xx8 MT xx8 Attachment H Page 80 of 84 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021...

Page 81: ...Attachment H Operating Instructions ET xx8 MT xx8 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021 Page 81 of 84 24 1 3 EAC...

Page 82: ...Operating Instructions ET xx8 MT xx8 Attachment H Page 82 of 84 R STAHL HMI Systems GmbH OI_ET_MT xx8_en_V_01_02_03 docx 10 03 2021...

Page 83: ...T_MT xx8_en_V_01_02_03 docx 10 03 2021 Page 83 of 84 25 Appendix I 25 1 Release notes The chapter entitled Release Notes contains all the changes made in every version of the Operating Instructions Ve...

Page 84: ...f Grimme Allee 8 D 50829 Cologne T Sales Support 49 221 768 06 1000 Technical Support 49 221 768 06 5000 F 49 221 768 06 4100 E Sales Support sales dehm r stahl com Technical Support support dehm r st...