Maintenance and Repair
12
225034 / 7570609300
2014-01-21·BA00·III·en·00
SolConeX Plug, 16 A
Series 7570/12
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
10
Maintenance and Repair
10.1 Maintenance
• Consult the relevant national regulations to determine the type and extent of
inspections.
• Adapt inspection intervals to the operating conditions.
During maintenance of the device, check at least:
• if the cables are clamped properly,
• if the permissible temperatures are adhered to (according to IEC/EN 60079),
• if there are signs of damage to the enclosure or the seals,
• if detachable connections such as screws are tight.
10.2 Maintenance
WARNING
Unauthorized work being performed on the device!
Risk of injuries and material damage!
• Work performed on the device must only be carried out by
appropriately authorized and trained personnel.
WARNING
Danger due to live components!
Risk of severe injuries!
• Disconnect all connections and cables from the power supply.
• Secure the connections against unauthorized switching.
Observe the relevant national regulations in the country of use.
• To avoid corrosion, the plug must be pulled regularly.
• If required, clean the plug pins
• After 1000 switching cycles, it is recommended to clean and then
lubricate using the lubricating oil KLÜBERALFA KRA 3-730.
It is not allowed to use lubricating greases based on mineral oils!
Summary of Contents for SolConeX 7570/12 Series
Page 2: ......
Page 16: ...14 225034 7570609300 2014 01 21 BA00 III de 00 SolConeX Stecker 16 A Reihe 7570 12 ...
Page 30: ...14 225034 7570609300 2014 01 21 BA00 III en 00 SolConeX Plug 16 A Series 7570 12 ...
Page 31: ......
Page 32: ...225034 7570609300 2014 01 21 BA00 III de en 00 ...
Page 33: ......