SolConeX extra-low voltage plug
Series 8573/12
8
Commissioning
Before commissioning, ensure the following:
• Check the mounting and installation.
• Enclosure must not be damaged.
• Remove any foreign bodies.
• If necessary, clean the connection chamber.
• Check if the conductors have been inserted correctly.
• Check whether all screws and nuts have been tightened firmly.
• Check whether all conductors have been clamped firmly.
• Observe the line voltage.
9
Operation
The plug can be used with the following products of R. STAHL:
• Wall-mounting socket 8573/13 (predecessor 8575/13)
• Flange socket 8573/15
• Coupling 8573/14 (predecessor 8575/14)
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation before commissioning.
• Comply with national regulations.
DANGER
Explosion hazard due to malfunction of the device after a short circuit in
the electric circuit!
Non-compliance results in severe or fatal injuries.
• Check the functionality of the plug after a short circuit.
• Replace defective devices immediately.
The plug may only be used when fully mounted.