background image

FLUES

Flues should be vertical wherever possible and
where a bend is necessary, it should not make an
angle of more than 45

o

with the vertical.  Horizontal

flue runs should be avoided except in the case of a
back outlet from the appliance, when the length of
the horizontal section should not exceed 150mm.

CHIMNEY

Do not connect to a chimney serving another
appliance.

The stove is a radiant room heater and must be con-
nected to a chimney of the proper size and type.

The chimney must have a cross-sectional area of at
least 30 square inches 19350sq. mm or a diameter
of at least 6” (150mm).  It is best to connect to a
chimney of the same size, as connection to a larger
size may result in a somewhat less draught.  

A flue that has proved to be unsatisfactory, particu-
larly with regard to down draught should not be used
for venting this appliance until it has been examined
and any faults corrected.  An existing masonry chim-
ney should be inspected and if necessary repaired
by a competent mason or relined using an approved
lining system.

The stove must  be connected to a chimney with a
minimum continuous draught of 0.06 w.g.  Poor
draught conditions will result in poor performance.

All register plates, restricter plates, damper etc.,
which could obstruct the flue at a future date should
be removed before connecting this appliance.

If connecting to an existing chimney with a flue
diameter of more that 8” it is recommend to line the
flue using a suitable stainless steel flue liner.

Where a masonry chimney is not available a propri-
etary type of 6”/150mm - twin wall, fully insulated
pipe may be used.  The pipe must terminate at a
point not lower than the main ridge of adjacent out-
side obstructions.  With such installation, access to
the chimney must be provided for cleaning purpos-
es.  

A chimney / flue termination must be located to min-
imise wind effects, a basic guide is that the distance
from the termination to the roof should be at be at
least 2300mm when measured horizontally and at
least 1000mm when measured vertically, (see
Fig.8). In circumstances where there are adjoining
buildings/ structures/ roof openings there are addi-
tional requirements, please refer to building regula-
tions part J.

8

2300

1000

Fig.8

Appliance

Soot Door

FLUE EXIT (TOP & REAR)

The stove is designed to allow  the chimney be
cleaned through the stove. If  the chimney cannot be
cleaned through the stove it is necessary to provide
a soot box/access door in the flue for cleaning.  See
Fig.9 for recommended locations.  Fit it to the stove
as shown in Fig.9.

Fig.9

Flue Liner

Flue

Soot Door

Debris Collection
space

Sleeve

Flue Pipe

Possible
Positions
for access

Appliance Flue
Outlet

Appliance

Summary of Contents for Erin

Page 1: ...rsons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations where children aged and or infirm persons are present a fireguard must be used to prevent accidental contact with the stove The fireguard should be manufactured in accordance with BS 8423 2010 PLEASE RETAIN ...

Page 2: ... 12 17 Floor Protection 12 18 Stove Dimensions 13 19 Commissioning Handover 13 20 Operation 13 21 Air Controls 13 22 Recommended Fuels 14 23 Technical Data 15 24 Lighting 15 25 User Instructions 15 26 De Ashing Refuelling 16 27 Slow Burning 16 28 Disposal of Ashes 16 29 Monthly Maintenance 16 33 Periodic Maintenance 16 30 Door Latch Adjustment 16 31 Chimney Cleaning 17 31 Glass Cleaning 17 31 Vitr...

Page 3: ...aught related issues external to the stove inadequate venting or ventilation excessive flue offsets negative air pressure caused by insufficient burning of improper fuel Damage caused to the unit while in transit Enamel discolouration due to over firing enamel damage caused by impact damage to baffles caused by over firing and fading of surface finish on casting Stress fractures on bricks Rust on ...

Page 4: ...8 Access should be provided to the chimney serving the appliance to allow for cleaning 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any room with a solid fuel appliance Location 10 Clearance to combustible materials must be adhered to as described in the Clearance to Combustible section 11 The stove must be installed on a floor protector that covers the a...

Page 5: ...r allow a build up of ashes in the ash pan as this will cause the grate to burn out prematurely Empty the ashpan when refuelling 7 Avoid slow burning of damp or unseasoned fuel as this will result in tarring flue ways and chim ney i e peat or timber 8 Allow adequate air ventilation to ensure plenty of air for combustion 9 Do not burn rubbish household plastic 10 Do not operate the stove with the a...

Page 6: ...si bility of disturbing any asbestos in the course of installation then please seek specialist guidance and use appropriate protective equipment Metal Parts When installing or servicing this stove care should be taken to avoid the possibility of personal injury IMPORTANT WARNING This stove must not be installed into a chimney that serves any other heating appliance The complete installation must b...

Page 7: ...nnecting rod through the control rod bracket with the notches facing downwards and leave it hanging loose until the stove is standing upright See Fig 5 Fig 5 G Remove the four M10 bolts from the base and fit the four legs using the four M10 x 20mm long bolts and the 3 8 washers pro vided in the jiffy bag See Fig 6 Fig 6 H Stand the stove upright taking care not to strain the back leg bolts Attach ...

Page 8: ...which could obstruct the flue at a future date should be removed before connecting this appliance If connecting to an existing chimney with a flue diameter of more that 8 it is recommend to line the flue using a suitable stainless steel flue liner Where a masonry chimney is not available a propri etary type of 6 150mm twin wall fully insulated pipe may be used The pipe must terminate at a point no...

Page 9: ... properly seated on the stove flue outlet Tighten screws See Fig 21 Fig 11 DOWN DRAUGHTS However well designed constructed and positioned the satisfactory performance of the flue can be adversely affected by down draught caused by near by hills adjacent tall buildings or trees These can deflect wind to blow directly down the flue or create a zone of low pressure over the terminal A suitable termin...

Page 10: ...ls should include a continuous duct across the cavity The duct should be installed in such a manner as not to impair the weather resistance of the cavity Joints between air vents and outside walls should be sealed to prevent the ingress of moisture Existing air vents should be of the correct size and unob structed for the appliance in use If there is an extraction fan fitted in adjacent rooms wher...

Page 11: ...ANDOVER On completion of the installation allow a suitable period of time for any fire cement and mortar to dry out when a small fire may be lit and checked to ensure the smoke and fumes are taken from the stove up the chimney and emitted safely to the atmosphere Do not run at full output for at least 24 hours Ensure that the operating instructions for the stove are left with the customer Ensure t...

Page 12: ...nd kept as dry as possible prior to use This appliance has been tested using seasoned wood logs and manufactured briquetted smokeless fuel Ancit for closed appliances sized between 20g and 140g Other fuels are commercially avail able and may give similar results Wood logs up to 340mm long are suitable All fuels should be stored under cover and kept as dry as possible prior to use Do not use fuels ...

Page 13: ...e from any obstructions As part of the stoves commissioning and handover the installer should demonstrate how to operate the stove correctly USER INSTRUCTIONS LIGHTING THE STOVE 1 Open firedoor and open the primary air inlet by sliding the control knob on the ashpit door to the right hand side 2 Open the secondary air inlet by pulling it out and open the air wash control by turning it anti clockwi...

Page 14: ...ox with fuel up to the maximum height just below the top of the fire fence at the front of the door opening Close all controls fully DE ASHING When ash build up becomes excessive in the fire chamber shake the firebars by inserting the operat ing tool into the square slot on the right side of the stove See Fig 20 DISPOSAL OF ASHES Your stove is provided with a steel ashpan This ash pan should be em...

Page 15: ...aged 4 Replace the hob before relighting the fire PERIODIC MAINTENANCE Fig 23 Hob Screws Cleaning Firebox Chamber Fig 22 ADJUSTING THE DOOR CATCH Over time the fire door latch can loosen due to the continual compression and hardening of the rope seal between the door and the front casting The position of the latch can be easily adjusted in order to tighten the door closure by removing the nut hold...

Page 16: ...the stove is cold by removing any dust or dirt using a dry cloth Do not use any water on the matt black senotherm finish as this will cause it to rust DO NOT USE ABRASIVE PADS OR OVEN CLEANSERS CONTAINING CITRIC ACID ON ENAMELLED SURFACES ENSURE THAT THE CLEANSER MANUFACTURERS INSTRUCTIONS ARE ADHERED TO NOTE Small impact marks on the enamel finish can be repaired using an appropriate enamel touch...

Page 17: ...er firing will also damage painted or enamel finish 3 Install a smoke detector in the room 4 A conveniently located class A fire extinguisher to contend with small fires resulting from burning embers 5 A practical evacuation plan 6 A plan to deal with a chimney fire as follows a Notify the fire department b Prepare occupants for immediate evacua tion c Close all openings into the stove Fig 26 CO A...

Page 18: ...ICK H00014AXX 34 RH FRONT BRICK H00015AXX 35 FIRE BRICK BOTTOM LEFT H00016AXX 36 BOTTOM SIDE BRICK RH H00017AXX 37 SERIAL NUMBER PLATE N00234BXX 38 DATA PLAQUE N00476AXX 39 PRIMARY AIR BOX Q00028AXX 40 PRIMARY AIR SHUTTER Q00029AXX 41 FRONT ROCKER BAR CLAMP Q00030AXX 42 SHAKER BARREL Q00037AXX 43 FRONT ROCKER BAR Q00044AXX 44 BACK ROCKER BAR Q00045AXX 45 ROCKER BAR FRAME Q00047BXX 46 FIRE FENCE RE...

Page 19: ...19 NOTES ...

Page 20: ...Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 Item No N00229AXX YS 150517Rev 018 20 ...

Reviews: