Model SCSS-700 Installation Manual
9-22
53722
Table 9-4: Menu choices for Internal/External Power Module
Choices
Type Selections
Function
Selections for
each Type
Comments
Enter Point or Circuit
Select Type
UNUSED
B NOTIF
NOTIF OUT
User also has Supervised/
Unsupervised option
CTRL CKT
A NOTIF
Same as B NOTIF
AUX PWR
CONSTANT
Constant auxiliary power.
RESETTABLE
Resettable auxiliary power.
DOOR
Door holder auxiliary power.
B SWITCH
MAN PULL
Refer to comments column of Table 9-
3 for description of these options.
Latch or Non-latching feature only
appears for waterflow, supervisory,
tamper, zone aux1, zone aux2, system
aux1, and system aux2.
WATERFLOW
SUPERVSY
TAMPER
FIREDRILL
SILENCE
RESET
PAS_ACK
ZN_AUX1
ZN_AUX2
SYS_AUX1
SYS_AUX2
MAN REL
ILOCK
A SWITCH
Same as B SWITCH
B DETECTOR
2-WIRE SMK
Used for Class B, 2-wire detectors.
4-WIRE SMK
Used for Class B, 4-wire detectors.
A DETECTOR
2-WIRE SMK
Used for Class A, 2-wire detectors.
4-WIRE SMK
Used for Class A, 4-wire detectors.
Select Zone/Group
Group or Zone selection will appear
depending on the type selected.
Edit Name
See Section 9.2.1.1.
Summary of Contents for SCSS-700
Page 2: ......
Page 12: ...SCSS 700 Installation Manual 8...
Page 22: ...Model SCSS 700 Installation Manual 1 10 53722...
Page 26: ...Model SCSS 700 Installation Manual 2 4 53722...
Page 31: ...Before You Begin Installing 53722 3 5 Figure 3 1 Wire Routing Example...
Page 42: ...Model SCSS 700 Installation Manual 3 16 53722...
Page 92: ...Model SCSS 700 Installation Manual 4 50 53722...
Page 148: ...Model SCSS 700 Installation Manual 8 26 53722...
Page 192: ...Model SCSS 700 Installation Manual 9 44 53722...
Page 250: ...SCSS 700 Installation Manual A 14 53722...
Page 254: ...Cut Along the Dotted Line...
Page 256: ......
Page 257: ......