background image

22

CHIMNEY CLEANING

The chimney should be cleaned twice annually or if
the stove is not used for a prolonged period during
the summer period, it should be cleaned prior to
commencement of usage. The chimney can be
cleaned through the stove depending on the flue
configuration and the flue liner should be cleaned in
accordance with manufacturer's instructions. Always
use a brush with plastic bristles that is the correct
size to reach all areas of the flue.

GLASS CLEANING

The stove glass will self-clean when there is suffi-
cient heat generated by the burning fuel i.e. when
the unit is operated at the maximum air settings. If a
build-up of creosote occurs on the glass it may be
due to low draft conditions, poor quality fuel or oper-
ating the stove at the minimum air settings for long
periods of time. The glass should be cleaned when
cool and cleaned with a non-abrasive cloth using
warm soapy water. For stubborn deposits, a grade 0
steel wool can be used whilst taking care not to
scratch the glass with any coal/ash deposits.

CLEANING A MATT BLACK/SENOTHERM
STOVE

Cleaning should be done when the stove is cold by
removing any dust or dirt using a dry cloth. Do not
use any water on the matt black/senotherm finish as
this will cause it to rust.

PROLONGED PERIODS OF NON USE

If the stove is to be left unused for a prolonged peri-
od of time then it should be given a thorough clean
to remove ash and unburned fuel residues. To
enable a good flow of air through the appliance to
reduce condensation and subsequent damage,
leave the air controls fully open.

It is important that the flue connection, any appliance
baffles or throat plates and the chimney are swept
prior to lighting up after a prolonged shutdown 
period.

WARNING NOTE:

Properly installed, operated and maintained this
stove will not emit fumes into the dwelling.
Occasional fumes from the de-ashing and re-
fuelling may occur. However, persistent fume emis-
sion is potentially dangerous and must not be toler-
ated. If fume emission does persist, then the follow-
ing immediate action should be taken:

(a) Open doors and windows to ventilate room.

(b) Let the fire out or eject and safely dispose of 

fuel from the stove.

(c)  Check for flue or chimney blockage and clean if

required.

(d)  Do not attempt to relight the fire until the cause

of the fume emission has been identified and 
corrected.  If necessary seek expert advice.

The most common cause of fume emission is flue-
way or chimney blockage. For you own safety these
must be kept clean at all times.

FIRE SAFETY

To provide reasonable fire safety, the following
should be given serious consideration.

1. Do not over fire the stove.
2. Over-firing will also damage painted or enamel

finish.

3. Install a smoke detector in the room.
4. A conveniently located class A fire extinguisher to

contend with small fires resulting from burning 
embers.

5. A practical evacuation plan.
6. A plan to deal with a chimney fire as follows:-

(a) Notify the fire department.

(b) Prepare occupants for immediate evacua-

tion.

(c) Close all openings into the stove.

(d) While awaiting the fire department watch for

ignition to adjacent combustibles from over- 

heated flue pipe or from embers or sparks 

from the chimney.

Summary of Contents for Solis Inset 500

Page 1: ...hould be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the stove in situations where children aged and or infirm persons are present a fireguard must be used to prevent accidental contact with the stove The fireguard should be manufactured in accordance with BS 8423 2010 PLEASE RETAIN ...

Page 2: ...15 Location 13 16 Clearance To Combustibles 13 17 Technical Data 14 18 Floor Protection 15 19 Stove Dimensions 500 Model 16 20 Stove Dimensions 900 Model 17 21 Commissioning and Handover 18 22 Operation 18 23 Air Controls 18 24 Recommended Fuels 18 25 Technical Data 19 26 Lighting 19 27 Installing the Solid Fuel Kit 500 900 Models 20 28 Lighting The Stove 20 29 Air Controls 21 30 Refuelling 21 30 ...

Page 3: ...3 TABLE OF CONTENTS PAGE NO 38 Fire Safety 22 39 Glass Replacement 23 40 CO Alarm 23 41 Exploded View 500 Model 24 42 Exploded View 900 Model 25 ...

Page 4: ...s per the requirements of the manual Failure to comply with the Installation requirements or Building Regulations will void your warranty Waterford Stanley reserve the right to replace any part due to manufacturing defect that fails within the warranty period under the terms of the warranty The unit must be used for normal domestic purposes only and in accordance with manufacturer s operation inst...

Page 5: ...ny other appliance 8 Access should be provided to the chimney serving the appliance to allow for cleaning This can be done through the stove 9 It is a requirement by Building Regulations to have a carbon monoxide alarm fitted to any room with a solid fuel appliance Location 10 Clearance to combustible materials must be adhered to as described in the Clearance to Combustible section 11 The stove mu...

Page 6: ...box riddle fully to remove all ashes This will allow better and cleaner burning See Re Fuelling section 6 Never allow a build up of ashes in the ash pan as this will cause the grate to burn out prematurely Empty the ashpan when refuelling 7 Avoid slow burning of damp or unseasoned fuel as this will result in tarring flue ways and chim ney i e peat or timber 8 Allow adequate air ventilation to ensu...

Page 7: ...e to do so may result in damage to persons and property Consult your local Municipal office and your insurance representative to determine what regulations are in force Save these instructions for future reference Please note that it is a legal requirement under England Wales Building Regulations that the installation of the stove is either carried out under Local Authority Building Control approv...

Page 8: ...y should be inspected and if necessary repaired by a competent mason or relined using an approved lining system The stove must be connected to a chimney with a minimum continuous draught of 0 06 w g Poor draught conditions will result in poor performance All register plates restrictor plates damper etc which could obstruct the flue at a future date should be removed before connecting this applianc...

Page 9: ...late by pulling it towards the fire door see Figure 5 and for the 900 model loosen the two front spigot fixing bolts see Figure 6 Fig 5 5 Remove the Flue Spigot by removing the four M8 Allen Screws and washers 6 Remove the Firebox Shell from the outer casing by loosening the two M6 Allen Head Screws and washers as shown in Figure 7 and pull the shell out from the casing 7 Drop the flue liner down ...

Page 10: ...NED CHIMNEY See Fig 9 1 Ensure that the opening is suitable for fitting of the inset stove Fig 3 shows 500 Model Fig 4 shows 900 Model 2 Ensure that the floor area is level 3 Remove the top baffle from the firebox by pulling it forward and lifting it up on the RHS to allow the LHS of the baffle to drop into the firebox so that it can be removed through the fire door opening 4 For the 500 model rem...

Page 11: ...wn the flue or create a zone of low pressure over the terminal A suitable terminal or cowl will usually effectively combat direct down blow but no cowl is likely to pre vent down draught due to a low pressure zone See Fig 10 Direction of wind Pressure zone Direction of wind Suction zone Pressure zone Direction of wind Pressure zone Suction zone Suction zone Fig 10 VENTILATION COMBUSTION AIR REQUIR...

Page 12: ...ll rate i e extrac tion fans tumble dryers with all external doors and windows closed If spillage occurs following the above operation an additional air vent of sufficient size to prevent this occurrence should be installed Especially Airtight Properties If the stove is being fitted in a property where the design air permeability is less than 5m3 h m2 nor mally newer properties built from 2006 the...

Page 13: ...ve a cross sectional area of at least 80cm2 LOCATION There are several conditions to be considered in selecting a location for your Solis Inset a Position in the area to be heated central locations are usually best b Allowances for proper clearances to combustibles c Allowances for proper clearances for mainte nance work Clearances to Combustibles This appliance must be installed in a recess the r...

Page 14: ...roval in Switzerland Fire Prevention Approval no 15202 Fire resistance DIN EN 13501 2 El 120 8O mm CE Certificate 0432 CPD 420002242 2 6 Construction material class DIN 4102 Non combustible A1 Bulk density 10 DIN EN 1094 4 250 kg m3 Porosity DIN EN 1094 4 Approx 90 Compressive strength DIN EN 1094 5 1 4 MPa Thermal conductivity at 200 C DIN EN 993 14 0 1 W mK Thermal expansion at 500 C DIN EN 993 ...

Page 15: ...ion Air Inlet Combustible Floor Heat thermal Insulation FLOOR PROTECTION It is recommended that the appliance is installed on a solid level concrete base of non combustible hearth conforming to the current Building Regulations which must extend 225mm in front of the unit and 150mm from the sides of the front edge This will provide protection from sparks and embers which may fall out when stoking o...

Page 16: ...16 STOVE DIMENSIONS 490 590 100 400 500 Model Fig 15 105 THREE SIDED FRAME 550 425 350 105 100 105 FOUR SIDED FRAME 490 645 550 425 350 100 105 ...

Page 17: ...5 95 75 425 555 95 350 85 100 FOUR SIDED FRAME 17 WARNING DO NOT OBSTRUCT PRIMARY AIR SUPPLY TO THE STOVE Note Dimensions stated are in millimetres unless otherwise stated and may be subject to a slight variation 645 675 425 350 555 100 85 ...

Page 18: ... hand lever located under the fire door Push right to open and left to close 2 The secondary air control lever is the left hand lever located under the fire door Push left to open and right to close Secondary Air Primary Air Fig 16 RECOMMENDED FUELS All fuels should be stored under cover and kept as dry as possible prior to use This appliance has been tested using seasoned wood logs If opting to b...

Page 19: ...Heat Output to Water Energy Efficiency Index Preferred Fuel Nominal Heat Output Net Efficiency Solis Inset 500 A 5 N A 110 Wood 5 82 Solis Inset 900 A 9 N A 107 Wood 9 80 LIGHTING Before lighting the stove check with the installer that the installation work and commissioning checks described previously have been carried out correctly and that the chimney has been swept clean is sound and free from...

Page 20: ...ing material in the firebed to light a new fuel charge excessive smoke emis sion can occur Refuelling must be carried out onto a sufficient quantity of glowing embers and ash that the new fuel charge will ignite in a reasonable period If there are too few embers in the fire bed add suitable kindling to prevent excessive smoke 9 The maximum amount of fuel specified in this manual should not be exce...

Page 21: ...uld damage the grate by overheating We recommend that you remove ashes after you have riddled the fire when the stove is thoroughly cooled 21 AIR CONTROLS Fuel Primary Air Secondary Air Primary Air Secondary Air Anthracite Smokeless Coal Fully Open Fully Closed 0 80 Open Fully Closed Ignition Controlled Burn Wood Turf Fully Closed Fully Open Fully Closed 0 80 Open MONTHLY MAINTENANCE Cleaning Stov...

Page 22: ...uce condensation and subsequent damage leave the air controls fully open It is important that the flue connection any appliance baffles or throat plates and the chimney are swept prior to lighting up after a prolonged shutdown period WARNING NOTE Properly installed operated and maintained this stove will not emit fumes into the dwelling Occasional fumes from the de ashing and re fuelling may occur...

Page 23: ... CO Alarm must be fitted either inside each bedroom or within 5 metres of the bedroom door refer to Building Regulations Part J Further guidance on the installation of a carbon monoxide alarm is available in BS EN 50292 2002 and from the alarm manufac turers instructions Provision of an alarm must not be considered a substitute for either installing the appliance correctly or ensuring regular serv...

Page 24: ...BRICK 093 30 008 12 RH SIDE BRICK 093 30 007 13 LH BASE BRICK 093 30 001 14 REAR BASE BRICK 093 30 003 15 RH BASE BRICK 093 30 002 16 BOTTOM BACK BRICK 093 30 004 17 TOP BACK BRICK 093 30 005 18 BOTTOM BACK BRICK FIXING BRACKET 093 30 009 19 CHROME DOOR TRIM 093 01 040 20 FLUE RESTRICTOR PLATE 093 00 005 21 FLUE RESTRICTOR PLATE FIXING BRACKET 093 08 000 22 SPRING LOADED LOCKING MECHANISM SET 093 ...

Page 25: ...0 9 OSA CONNECTION 099 06 000 10 FLUE SPIGOT 099 06 005 11 LH SIDE BRICK 099 09 001 12 RH SIDE BRICK 099 09 002 13 LH BASE BRICK 099 09 004 14 RH BASE BRICK 099 09 004 15 LH BACK BRICK 099 09 005 16 RH BACK BRICK 099 09 006 17 AIR CONTROL LEVER PRIM SET 099 05 023 19 STAINLESS DOOR TRIM 099 03 019 20 FLUE RESTRICTOR PLATE 099 10 004 21 FLUE RESTRICTOR PLATE FIXING BRACKET 099 10 002 22 SPRING LOAD...

Page 26: ...26 NOTES ...

Page 27: ...27 NOTES ...

Page 28: ...28 Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 Rev 005 SG 051018 ...

Reviews: