background image

11

Fig.10

DHW PLUMBING SYSTEM

in the unlikely event that the appliance is not operat-
ing in freezing conditions the water must be drained
from the boiler to prevent frost damage.

DOMESTIC HOT WATER SYSTEM
(DHW MODEL ONLY)

The DHW Model must be connected to a gravity
system.  Care should be taken to ensure that the
domestic hot water installation is correctly installed
and that it complies with all relevant codes of prac-
tice. If this appliances is being connected to an exist-
ing system, it is strongly recommended to check the
following:

(a) That the system is sound.
(b) That the pipe work is adequately insulated. 
(c) Are there any modifications necessary to
make the domestic hot water system more
efficient.

SAFETY VALVE

A non-adjustable 3 bar safety valve must be fitted to
the primary flow pipe adjacent to boiler connection
ensuring that any discharge will not create a hazard
to occupants or cause damage to electrical compo-
nents or property.

NOTE: 

We strongly advise the use of pipe lagging

if the installation is likely to be exposed to situations 
where the temperatures will drop to a level consis-
tent with frost.

Only competent personnel should be employed to
carry out any work on your domestic hot water sys-
tem.

DIRECT DOMESTIC CYLINDER

A 227 Litre (60 Gallon) direct domestic cylinder can
be connected to this cooker using copper or stain-
less steel 28mm O.D. (1”) flow & return pipes. We
recommend that the cylinder is lagged along with
the pipework. We do not recommend the use of a 
direct cylinder in areas where there is a high 
concentration of lime or minerals in the water.

INDIRECT DOMESTIC CYLINDER

A 227 Litre (60 Gallon) indirect domestic cylinder
can be connected to this cooker using copper or
stainless steel 28mm O.D (1”) flow and return pipes.
We recommend that the cylinder is lagged along the
pipework.

INJECTOR TEE

Where the gravity and central heating circuits join
together to return to the stove we recommend the
use of an injector tee connection, situated as close
to the unit as possible.  This type of tee encourages
a stable flow of  water through both circuits and
helps to prevent priority being given to the stronger
flow, which is most commonly the pumped central
heating circuit.  

WATER CIRCUIT TEMPERATURE

The return water temperature should be maintained
at not less than 40°C so as to avoid condensation on
the boiler and return piping.  Fitting a pipe thermo-
stat to the flow pipe of the gravity circuit and wiring it
into the pump control will ensure rapid circulation of
the hot water.

In some circumstances it may be possible to over-
heat the appliance and the water inside will boil.
This will be evident by the sound of a knocking noise
coming from the appliance and pipes around the
house.  If this occurs close off all air controls and
manually start the central heating pump if fitted.
One radiator on the heating circuit should be uncon-
trolled to act as a heat leak in the event that the
appliance overheats and has nowhere to discharge
a build up of hot water should the heating circuit be
satisfied.  Be aware that steam and boiling water
willl be expended from any open vent from the heat-
ing system probably in the roof space at the expan-
sion tank. 

Summary of Contents for Tara Boiler

Page 1: ...or infirm persons should be supervised at all times and should not be allowed to touch the hot working surfaces while in use or until the appliance has thoroughly cooled When using the boiler stove in situations where children aged and or infirm persons are present a fire guard must be used to prevent accidental contact with the stove The fireguard should be manufactured in accordance with BS 8423...

Page 2: ...8 Boiler Model 8 DHW Model 8 Non Boiler Model 9 14 Technical Data 9 15 Plumbing Boiler Model 10 16 Regulations 10 17 Gravity Circuit 10 18 Interlink System 10 19 DHW Plumbing 11 20 Injector Tee 11 21 Water Circuit Temperature 11 22 Domestic Hot Water System DHW Model Only 11 23 Safety Valve 11 24 Direct Domestic Cylinder 11 25 Indirect Domestic Cylinder 11 26 Pipe Thermostat 12 27 Handover 12 28 O...

Page 3: ...16 40 De Ashing 16 41 Disposal of Ashes 16 42 To Clean Chimney Outlet Boiler Non Boiler Model 17 43 To Replace Fire Grate 17 44 Fire Safety 17 45 Vitreous Enamel Cleaning 17 46 Glass Cleaning 18 47 Glass Replacement 18 48 Data Plaque Position 18 49 CO Alarm 18 50 Exploded View HPB Stove 19 51 Exploded View NB Stove 20 52 Exploded View DHW Stove 21 53 Installation Check List 22 3 ...

Page 4: ...protective equipment Metal Parts When installing or servicing this stove care should be taken to avoid the possibility of personal injury IMPORTANT WARNING This stove must not be installed into a chimney that serves any other heating appliance There must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit fumes into the room 4 The complete installation ...

Page 5: ...flue termination point should be located a minimum of 1000mm from the roof measured vertically and 2300mm measured horizontally Where this termination point does not suffice it may be necessary to extend the flue pipe so that the termination point is above the apex See Fig 3 2300 1000 Soot Door Appliance Fig 3 FLUE PIPES A flue pipe should only be used to connect an appli ance to a chimney and sho...

Page 6: ... All materials used in the manufacture of air vents should be such that the vent is dimensionally stable and corrosion resistant The effective free area of any vent should be ascer tained before installation The effect of any screen should be allowed for when determining the effective free area of any vent Air vents direct to the outside of the building should be located so that any air current pr...

Page 7: ...n use Where such a installation exists a test for spillage should be made with the fan or fans and other appli ances using air in operation at full rate i e extrac tion fans tumble dryers with all external doors and windows closed If spillage occurs following the above operation an additional air vent of sufficient size to prevent this occurrence should be installed PERMANENT AIR VENT The stove re...

Page 8: ...Fig 7 SPECIFICATION DHW STOVE 8 Fig 7A BOILER STOVE ...

Page 9: ...2 1 4 1 5 5 6 5 6 3 Output to Water kW 5 9 5 4 N A N A 2 7 3 Typical Refuel Interval To Achieve Nominal Outputs h 4 15 1 4 1 5 1 0 75 Mean Flue Gas Temp o C 264 240 250 250 245 286 Gross Weight kg 147 135 135 Max Water Pressure Bar 2 N A 2 Flue Outlet Diameter mm 152 152 152 Wood Log Size mm N A 300 N A 300 N A 300 Note Dimensions stated are in millimetres and may be subject to a slight variation ...

Page 10: ...ould be connected to the boiler by 28mm diame ter flow and return piping The pipes should not exceed 7 8 meters 25ft in length and cylinder and pipework should be fully lagged The shorter the run of pipe work the more effective the water heating Fig 8 WARNING DO NOT OBSTRUCT PRIMARY AIR SUPPLY TO THE SPIN VALVE AT THE FRONT OF THE STOVE There must be no gate valves on this circuit and it must have...

Page 11: ...ct cylinder in areas where there is a high concentration of lime or minerals in the water INDIRECT DOMESTIC CYLINDER A 227 Litre 60 Gallon indirect domestic cylinder can be connected to this cooker using copper or stainless steel 28mm O D 1 flow and return pipes We recommend that the cylinder is lagged along the pipework INJECTOR TEE Where the gravity and central heating circuits join together to ...

Page 12: ...he operating instructions for the stove are left with the customer Ensure to advise the cus tomer on the correct use of the appliance with the fuels likely to be used on the stove and warn them to use only the recommended fuels for the stove Advise the user what to do should smoke or fumes be emitted from the stove The customer should be warned to use a fireguard to BS 6539 in the pres ence of chi...

Page 13: ...start or freshen up afire in this heater 9 When a hot bed of fuel is established add the normal fuel and adjust the spin valve to the required setting 10 To shut the fire down do not add fuel make sure that the firedoor is properly closed and that the primary and secondary air controls are all in the closed position Cutting off the air supply will reduce the heat output 11 Following a prolonged sh...

Page 14: ... this will over heat the unit causing unnecessary damage Close the ash door between removing and replacing the ashpan 9 Clean the chimney at least twice a year 10 Burning soft fuels such as timber and peat will stain the glass Regular cleaning will prevent per manent staining Clean with soapy water when cool 11 Keep all combustible materials a safe distance away from unit please consult manual for...

Page 15: ...cover and kept as dry as possible prior to use Do not use fuels with a Petro coke ingredient as this may cause the grate to overheat causing damage Reduced outputs will result when fuels of lower calorific values are used Never use gasoline or gasoline type lantern fuel kerosene charcoal lighter fluid or similar liquids to start or freshen up a fire in this heater Keep all such liquid well away fr...

Page 16: ...ont door Part No 2 When the ash is dis posed of replace the empty ashpan OPERATION To operate the Secondary Air push to open and pull to close Open secondary air slider only when the fire is established Note Close off the secondary air for overnight burn OVERNIGHT BURNING To achieve an overnight or a low burn rate close the Air Wash Shutter fully close the front spin valve fully or leave it open a...

Page 17: ... is finished in a high gloss vitreous enamel to keep the enamel in the best condition observe the following tips 1 Wipe over daily with a soapy damp cloth followed by a polish with a clean dry duster 2 For stubborn deposits a soap impregnated pad can be carefully used on the vitreous enamel 3 Only products recommended by the Vitreous Enamel Association these products carry the Vitramel label Non B...

Page 18: ...ement glass e Place the thermal tape side of the glass into the door recess and replace the four corner clips f Tighten screws g Replace glass only with ceramic glass 5mm thick DATA PLAQUE POSITION The data plaque is positioned at the back of the stove See Fig 21 Fig 21 CO ALARM Waterford Stanley recommend the fitting of a CO Alarm in the same room as the appliance this is a requirement under UK B...

Page 19: ...HUTTER Q00247AXX 15 AIR WASH PLATE Q00564AXX 16 FLUE BLANKING PLATE Q00624AXX 17 GLASS WINDOW T00009BXX 18 DOOR HANDLE LONG U00009AXX 19 2 HINGE U00010AXX 20 AIR WASH KNOB U00077AXX 21 DOOR HANDLE AXLE V00022BXX 22 DOOR LATCH V00023AXX 23 SPACER TO DOOR HANDLE V00035AXX 24 SPRING RS 751 584 V00151AXX 25 AIR WASH SHUTTER SHAFT V00158AXX 26 M8 X 44 SPINDLE V00763AXX 27 PULL ROD V00992AXX 28 SPLIT PI...

Page 20: ...L H00197AXX 20 SERIAL NUMBER PLATE N00234BXX 21 DATA PLAQUE N00442AXX 22 OSA DAMPER GASKET P00101AXX 23 SECONDARY AIR WASH SHUTTER Q00247AXX 24 DRY SHELL PROTECTION PLATE Q00250AXX 25 AIR WASH PLATE Q00564AXX 26 GLASS WINDOW T00009AXX 27 DOOR HANDLE LONG U00009AXX 28 SECONDARY AIR CONTROL U00018AXX 29 AIR WASH KNOB U00077AXX 30 HINGE U00153AXX 31 DOOR HANDLE AXLE V00022BXX 32 DOOR LATCH V00023AXX ...

Page 21: ...ECTION PLATE Q00250AXX 19 AIR WASH PLATE Q00564AXX 20 FLUE BLANKING PLATE Q00624AXX 21 GLASS WINDOW T00009BXX 22 DOOR HANDLE LONG U00009AXX 23 2 HINGE U00010AXX 24 KNOB SECONDARY AIR DAMPER U00018AXX 25 AIR WASH KNOB U00077AXX 26 DOOR HANDLE AXLE V00022BXX 27 DOOR LATCH V00023AXX 28 SPACER TO DOOR HANDLE V00035AXX 29 SPRING RS 751 584 V00151AXX 30 AIR WASH SHUTTER SHAFT V00158AXX 31 SECONDARY AIR ...

Page 22: ...ble materials must be adhered to as described in the Clearance to Combustible section 8 The stove must be installed on a floor protector that covers the area under the stove and extends 18 to the front 8 to the sides and back Plumbing 9 Appliance must be connected to a gravity circuit using 1 ID flow return piping 10 The length of pipes from the cylinder to the cooker should not exceed 7 8 metres ...

Page 23: ...23 NOTES ...

Page 24: ...NOTES REV 002 DP 150309 N00154AXX Manufactured by Waterford Stanley Ltd Unit 401 403 IDA Industrial Estate Cork Road Waterford Ireland Tel 051 302300 Fax 051 302315 www waterfordstanley com 24 ...

Reviews: