Operating and service manual
Test Alarms (AL 8XX)
800
Func test failed
Alarm
Description
Function Test Fault
Cause
Trouble
shooting
Possible causes:
•
One or more of the individual test steps have failed.
Accompanied alarms:
•
AL 8XX.
Trouble shooting:
1) See individual AL 8XX alarms for cause
Criteria
One or more of the individual test steps have failed
Controller
action
FC will soon trip with error 516 and stop compressor
Log
X
Alarm
X
Alarm light
Slow flash
Consequence
Deteriorated control precision and capacity
Elimination
When currents are normal, it is marked as inactive in alarm list and may then be deleted.
Value must be valid for 30 sec. to set alarm inactive.
Log data
Parm 1
Parm 2
Parm 3
Parm 4
Parm 5
Active/Inactive ID
Test time [sec]
Alarms