23 of 222 pages
Operating and service manual
Fresh air exchange
Fresh air exchange
Adjustable 0 – 220 m3/h (0 – 129 CFM) at 60
Hz. adjustable by steps of 5 m3/h.
Equivalent to 0 - 170 m3/h (0 –100 CFM) at 50
Hz.
Refrigeration controls
Expansion valves
2 solenoid valves, electronically controlled by
the controller
Filter Drier
Danfoss DML 164 with O – ring or equivalent
Hot gas valve
Solenoid valve electronically controlled by the
controller
Moisture indicator
Incorporated in receiver sight glass.
Material: Brass acc. to EN 12164 / CW602N.
Piping
Solid copper tubes according to EN 12735 – 1
Pipe coating
Primer: Epoxy resin zf – a120.
Top coat: Polyurethane resin Hipon – 50.
Electrical data
Input power (operational)
3 x 360 V - 460 V 50Hz / 3 x 400 V - 500 V 60
Hz
Control circuit voltage AC
24 Vac Nominal (varies with power supply).
18 Vac (350 V) - 30 Vac (500V).
Control circuit voltage DC
24 V DC Nominal (varies with power supply).
15 V DC (350 V) - 30.5 V DC (500V).
Circuit Breaker
Main power ampere
25 A or 16 A
Contactors
Nominal
9 amp at 40°C (104°F) & 400 volt
Max
7 amp at 70°C (158°F) & 520 volt
Start current
6 x nominal
Fuses
Secondary main fuses
10 A, tube fuse
Control circuit supply
0.4 A, tube fuse
24 V AC circuit
6.3 A, tube fuse
Power plug
Type
CEE 17.4 pole, with earth. 32 amp
400/460 V / 50/60 Hz