T03 Abort the running test (Abort the test)
Function:
Stop the running PTI or function- test.
Value:
To stop the running test, STOP must be highlighted by pressing . Pressing
once more stops
the test.
T04 Test status (Test status)
Function:
Shows the status of the last/running test:
Value:
The value depends on the function running.
For PTI the values can be: “RUN” for running, “PASS” for test passed successfully, “ABORT” for
test aborted by a user, “FAIL” for a failing PTI test – see the alarm list for specific reason.
T05 Test result: 10 Init (10 Init)
Function:
Shows the status of the test initialization. This test is always done
Value:
“-“ if not done yet. “RUN” if still running test. “PASS” if test finished successfully. “FAIL” if the test
failed. “ABORT” if the test was aborted by the user.
T06 Test result: 20 Controller (20 Controller)
Function:
Shows the status of the test of the controller.
Value:
“-“ if not done yet. “RUN” if still running test. “PASS” if test finished successfully. “FAIL” if the test
failed. “ABORT” if the test was aborted by the user. See specific description for alarm 801 in
Test
alarms
p.149.
T07 Test result: 30 Power (30 Power)
Function:
Shows the status of the test of power consumption/connection.
Value:
“-“ if not done yet. “RUN” if still running test. “PASS” if test finished successfully. “FAIL” if the test
failed. “ABORT” if the test was aborted by the user. See specific description for alarm 805 in
Test
alarms
p.149.
T08 Test result: 40 Evap fan (40 Evap fan)
Function:
Shows the status of the test of the evaporator fans.
Value:
“-“ if not done yet. “RUN” if still running test. “PASS” if test finished successfully. “FAIL” if the test
failed. “ABORT” if the test was aborted by the user. See specific description for alarm 810 - 813 in
Test alarms
p.150.
T09 Test result: 50 Condenser fan (50 Cond fan)
Function:
Shows the status of the test of the condenser fan.
Value:
“-“ if not done yet. “RUN” if still running test. “PASS” if test finished successfully. “FAIL” if the test
failed. “ABORT” if the test was aborted by the user. See specific description for alarm 815 - 817 in
Test alarms
p.152
T10 Test result: 60 Evaporator heater (60 Evap heater)
Function:
Shows the status of the test of the evaporator heater.