Operating and service manual
127
Tamb open
Warning
Description
Ambient Temperature Sensor Open Circuit
Cause
Indication of loose connection, defective or lack of ambient temperature sensor
Trouble
shooting
Possible causes:
•
Temperature sensor Tamb or its cable defective.
•
X1 cable is defective.
•
Controller PCB defective.
Accompanied alarms:
•
AL 129.
Trouble shooting:
1) Disconnect the sensor cable for sensor Tamb from the connector on the
interface/terminal block PCB, according to the wiring schematics inside in
the control cabinet.
2) Measure the resistance between the two wires.
a) If the resistance is more than 1.5 MΩ, the cable or the sensor is defect,
replace sensor and cable.
b) If the resistance matches the resistance and temperature in table,
Tables
starting p.204, the temperature sensor and cable are ok.
3) Measure the voltage over the connector for Tamb. It should be between 4.80
and 5.05V DC
a) If the voltage is inside the above range, connect sensor again. Measure the
voltage over the sensor and check voltage/temperature according to table in
Tables
starting p.204.
b) If the voltage is outside the above range, the controller PCB is defect or
other sensors may be defect and pulling the voltage down. Check other
alarms and see
Trouble shooting for Star Cool Controller
p.56 before
replacing controller door.
Criteria
Value below low alarm limit -60°C (-76°F)
Controller
action
Replacement by new value from AAS system
Log
X
Alarm
X
Alarm light
Off
Consequence
No consequence as to control
Elimination
When sensor value becomes valid, it is marked as inactive in the alarm list and may then
be deleted.
Log data
Parm 1
Parm 2
Parm 3
Parm 4
Parm 5
Active/Inactive Low limit
High limit
Current