Press sensor type
Alarm
Description
Saved FC ID does not match the current FC ID
Cause
Replaced Frequency Converter or controller door
Trouble
shooting
Possible causes:
Accompanied alarms:
•
AL 207 and AL 611
Trouble shooting:
1. Manually select the type of pressure transmitters in the configuration on
menu F07 and F08.
Criteria
The saved Frecuency Converter ID does not match the new Frecuency Converter ID in
the controller.
Controller
action
Replacement by new value from AAS system.
Log
X
Alarm
X
Alarm light
On
Consequence
The unit will continue operation with AAS value.
Elimination
The operator has to manually select the type of pressure transmitters in the
configuration on menu F07 and F08
Log data
Parm 1
Parm 2
Parm 3
Parm 4
Parm 5
Active/Inactive T0
Tc
Type Low
Type High