Performance Characteristics

 1. Rea

d all instructions before beginning installation.        

  2.  Be sure the installation does not exceed a maximum 

of 15 feet of vertical lift.                     

  3.  Be sure the pump is level within 1/8" for the length of 

the condensate pump.

  4.  Use soapy water when cleaning unit. Refer to 

maintenance guidelines. 

                    

  5.  For best results, drain and discharge lines should 

have a continuous downward slope.

  1.  DO read all installation material included with the 

pump.

                      

  2.  DO inspect unit for any visible damage caused 

by shipping. Contact dealer if unit appears to be 

damaged.                         

  3.  DO clean all debris from the pump reservoir.   
  4.  DO always disconnect pump from power source 

before handling. DO always connect to a separately 

protected and properly grounded ground fault 

protected circuit. DO NOT ever cut, splice or 

Ten Helpful Hints For Easy Installation

Do’s  And  Don't’s  For  Installing  A  Unit

damage power cord.  DO NOT carry or lift pump by 

its power cord. DO NOT use an extension cord with 

this condensate pump.                       

  5.  DO NOT use

 

a discharge pipe smaller than the 

pump discharge size.                       

  6.  DO test pump immediately after installation to be 

sure that the system is working properly.                       

  7.  DO review all applicable local and national codes 

and verify that the installation conforms to each of 

them. 

  6.  Test operation of pump per STEP 5.
  7.  Do not overtighten check valve after cleaning. 

Refer to maintenance guidelines.

  8.  Plug pump into a constant voltage source. Do not 

plug into a device that runs intermittently.

  9.  The model number and date code can be found on 

the cord warning label.

 10. For best results, the highest point of the discharge 

line should be higher than 5’ above floor.

10 

20 

80 

30 

40 

160 

50 

240 

60 

70 

80 

12 

15 

21 

TOT

AL

 DYNAMIC HEAD 

METERS 

FEET

 

FLOW PER HOUR 

GALLONS 
LITERS 

18 

IL0540 

PUMP PERFORMANCE CURVE

MODEL COND-1

TOTAL DYNAMIC HEAD/FLOW 

PER HOUR CONDENSATE

MODEL

COND-1

Feet

Meters

Gal.

Liters

3

.9

76

288

6

1.8

68

257

9

2.7

60

227

12

3.7

43

163

15

4.6

21

79

Shut-off head:

18 ft. (5.5m)

Summary of Contents for COND-1

Page 1: ...ng 2 Carefully read all the literature provided to familiarize yourself with specific details regarding installation and use before attempting the installation These materials should be retained for future reference 1 Check to be sure your power source is adequate to handle the amperage requirements of the motor as indicated on the pump or unit I D tag 2 All plumbing discharge and drain lines must...

Page 2: ...R ANY CIRCUMSTANCES BE LIABLE FOR INCIDENTAL CONSEQUENTIAL OR SPECIAL DAMAGES SUCH AS BUT NOT LIMITED TO DAMAGE TO OR LOSS OF OTHER PROPERTY OR EQUIPMENT LOSS OF PROFITS INCONVENIENCE OR OTHER INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY TYPE OR NATURE THE LIABILITY OF THE MANUFACTURER SHALL NOT EXCEED THE PRICE OF THE PRODUCT UPON WHICH SUCH LIABILITY IS BASED This warranty gives you specific legal...

Page 3: ...lling A Unit damage power cord DO NOT carry or lift pump by its power cord DO NOT use an extension cord with this condensate pump 5 DO NOT use a discharge pipe smaller than the pump discharge size 6 DO test pump immediately after installation to be sure that the system is working properly 7 DO review all applicable local and national codes and verify that the installation conforms to each of them ...

Page 4: ...ward slope to allow for gravity flow Note Local codes may require the use of a condensate neutralizer when using this pump Note Make sure the drain lines from the A C condenser are supported above the reservoir and no weight from the drain line is directed to the bottom of the reservoir SK1762 STEP 1 Mounting Location STEP 2 Installation of Condensate Drain Lines SK1762 CONDENSING GAS FURNACE OVER...

Page 5: ...he highest point possible Refer to Figure 3 1 3 2 From this point direct the discharge line to the location of the main drain maintain a continuous downward slope Note If a continuous downward slope is not possible then make an inverted U at the highest point of the discharge line Note Make sure the 3 8 ID tube is supported in a way it will not Kink or Pinch off blocking flow Figure 3 1 SK1764 STE...

Page 6: ...on Highest point of discharge line is less than 5 Check Valve is too tight or too loose O ring damaged Plug in Have a qualified electrician check fuse circuit Be certain the appliance is generating condensate Check drain line s and or discharge line for blockage Contact Factory Check drain line s and or discharge line for blockage Refer to Maintenance Guidelines section for cleaning instructions R...

Page 7: ...7 Copyright 2018 Star Water Systems All rights reserved NOTES ...

Page 8: ......

Reviews: