background image

11

WATER SOFTENER TROUBLE SHOOTING

JUST INSTALLED UNIT AND WATER IS NOT SOFT

WHAT TO CHECK

HOW TO CORRECT

Has unit been properly installed

Re-read instructions to see that all steps were followed

By-pass in plumbing

On a 3-way by-pass valve system, open valves on piping 

coming into and out of softener. The valve in between 

MUST be closed and in good condition. Most units include 

a by-pass valve which is connected to the control valve. 

Make certain that it is in the service position.

Is unit piped in backwards

Check arrows where pipe threads into valve head and make 

sure water is flowing consistent with the direction arrows 

are pointing.

Hot water tank hardness

Allow sufficient time for hardness that has built up in your 

water heater and pipes to run through system. Repeated 

flushing of the water heater tank can also be done.

Is there resin in tank

Softeners ship with resin already in the tank. Make sure the 

resin has not been emptied or dumped. Put a trouble light 

behind resin tank and you should be able to see the resin 

thru the mineral tank. The tank should be approx. 2/3 full.

Valve head is not working correctly and causing water flow 

not to go through softener

Shut off water supply, de-pressurize the unit*, unscrew the 

valve head from unit and exchange it.

Softener has been undersized and does not effectively 

remove the amount of hardness in your water

Draw a sample of untreated water before it goes through 

the softener and a sample of treated water after the 

softener. Have the samples analyzed to see if any hardness 

is being removed.

Water flow rate going through the softener is not allowing 

time for the unit to soften

Open an outside faucet and fill a measured bucket up with 

water for 1 minute. The amount of gallons in the bucket tells 

you how many gallons per minute are being run through 

the softener. Call 1-800-545-2206 to see what the GPM 

limit is on the specific unit you have purchased. Add a flow 

control accessory to your unit if needed.

*To depressurize the unit, refer to valve instructions for your particular unit.

WATER TASTES SALTY OR BRINE TANK FILLS WITH WATER

WHAT TO CHECK

HOW TO CORRECT

Is backwash water flowing freely down to drain with an air 

gap and no back siphoning

Put valve into “Backwash” position and follow water flow 

down to drain. If over 20 ft., use 3/4” (or larger) drain 

tubing. Drain line should be no more than 8 ft. lift.

Brine salt tube and connections not allowing salt solution 

into mineral tank to regenerate

Visually check tubing for cracks or kinks. Check fittings for 

proper assembly and tightness as diagrammed.

Brass
Compression
Nut

Brass
Insert

Plastic
Ferrule

Poly
Tubing

IL0707

Injector or injector screen plugged

Put softener in by-pass position and de-pressurize the unit 

by putting into “Backwash” position. There will be 2 screws 

on neck of valve where the salt rinse line goes into softener. 

Remove the 2 screws and clean screen and remove any 

chunks of salt, etc.

Summary of Contents for S07EC24

Page 1: ...if the insulation were to become damaged The receptacle should be located four 4 feet above the basement floor to guard against the possibility of immersion Disconnect power at the main electrical bo...

Page 2: ...aker of 20 amps or less Do not run 1 2 I D semi rigid drain tube over 20 running feet If over 20 ft increase drain line tubing size to 3 4 I D for the entire length of tube Initially fill salt brine t...

Page 3: ...placing cabinet or tanks on 3 4 plywood and shim to level as needed 6 Locate the softener in the supply line BEFORE the water heater Temperatures above 100 F 38 C will damage the softener and void the...

Page 4: ...ters Scale buildup from hard water is dramatically increased when water is heated 4 Install the unit in the water line ahead of the water heater close to a drain and a 115 volt grounded outlet on a fl...

Page 5: ...an existing unit CAUTION Install in directions of arrows IL0635 11 Above diagram shows unit installed with a by pass valve The unit can be removed easily without disrupting the plumbing A 3 valve by p...

Page 6: ...ASS VALVE HEAT WILL DAMAGE PLASTIC PARTS Inlet Outlet Control Valve Copper Pipe Compression Fittings Sweat Fittings IL0704 Connecting to Copper Pipe 16 Turn fittings clockwise with a wrench to tighten...

Page 7: ...nk unit proceed to step 28 22 Loosen compression nut located on right side of control valve by turning counter clockwise Insert one end of 3 8 O D tube included NOTE This step has already been done on...

Page 8: ...the softener cabinet or brine tank and run to a suitable drain Do not connect to drain line off of softener 29 Plug cord from control valve into 115V grounded electrical outlet Make certain that outl...

Page 9: ...sure 1 1 2 oz of chlorine bleach and pour solution directly into the brine tank or salt compartment on single tank units 36 On all tank units pour salt into compartment Fill about 3 4 full initially D...

Page 10: ...DITIONERS OR FILTERS FROM FREEZING WHILE IN STORAGE NOTE The warranty does not apply to damage due to freezing nor is the manufacturer responsible for or assume any liability for breakage missing part...

Page 11: ...water Draw a sample of untreated water before it goes through the softener and a sample of treated water after the softener Have the samples analyzed to see if any hardness is being removed Water flow...

Page 12: ...Clean and unplug necessary line so water flows uninterrupted Brine salt line and connections not allowing salt solution into mineral tank to regenerate Visually check tubing for cracks or kinks Check...

Reviews: