background image

14

THERMAL EXPANSION

Water supply systems may, because of such events as high line
pressure, frequent cut-offs, the effects of water hammer among
others, have installed devices such as pressure reducing valves, check
valves, back flow preventers, etc. to control these types of problems.
When these devices are not equipped with an internal by-pass, and no
other measures are taken, the devices cause the water system to be
closed.  As water is heated, it expands (thermal expansion) and closed
systems do not allow for the expansion of heated water.

The water within the water heater tank expands as it is heated and
increases the pressure of the water system.  If the relieving point of
the water heater’s temperature-pressure relief valve is reached, the
valve will relieve the excess pressure.  

The temperature-pressure

relief valve is not intended for the constant relief of thermal
expansion.

  This is an unacceptable condition and must be corrected.

It is recommended that any devices installed which could create a
closed system have a by-pass and/or the system have an expansion
tank or device to relieve the pressure built by thermal expansion in the
water 

system.  Expansion tanks are available for ordering through a

local plumbing contractor.  Contact the local water heater supplier or
service agency for assistance in controlling these situations.

STRANGE SOUNDS

Possible noises due to expansion and contraction of some metal parts
during periods of heat-up and cool-down do not necessarily represent
harmful or dangerous conditions.

OPERATIONAL CONDITIONS

SMELLY WATER

In each water heater there is installed at least one anode rod (see
parts sections) for corrosion protection of the tank.  Certain water
conditions will cause a reaction between this rod and the water.  The
most common complaint associated with the anode rod is one of a
“rotten egg smell” in the hot water.  This odor is derived from hydrogen
sulfide gas dissolved in the water.  The smell is the result of four
factors which must all be present for the odor to develop:

A. A concentration of sulfate in the supply water.
B. Little or no dissolved oxygen in the water.
C. A sulfate reducing bacteria which has accumulated within the water

heater (this harmless bacteria is nontoxic to humans).

D. An excess of active hydrogen in the tank.  This is caused by the

corrosion protective action of the anode.

Smelly water may be eliminated or reduced in some water heater
models by replacing the anode(s) with one of less active material, and
then chlorinating the water heater tank and all hot water lines.  Contact
the local water heater supplier or service agency for further information
concerning an Anode Replacement Kit and this chlorination treatment.
If the smelly water persists after the anode replacement and chlorination
treatment, we can only suggest that chlorination or aeration of the
water supply be considered to eliminate the water problem.

Do not remove the anode leaving the tank unprotected.  By
doing so, all warranty on the water heater tank is voided.

“AIR” IN HOT WATER FAUCETS

HYDROGEN GAS: Hydrogen gas can be produced in a hot water
system that has not been used for a long period of time (generally two
weeks or more).  Hydrogen gas is extremely flammable and explosive.
To prevent the possibility of injury under these conditions, we
recommend the hot water faucet, located farthest away, be opened
for several minutes before any electrical appliances which are
connected to the hot water system are used (such as a dishwasher or
washing machine).  If hydrogen gas is present, there will probably be
an unusual sound similar to air escaping through the pipe as the hot
water faucet is opened.  There must be no smoking or open flame near
the faucet at the time it is open.

HIGH WATER TEMPERATURE SHUT OFF SYSTEM

A non-adjustable high temperature limit control operates before steam
temperatures are reached.  The high limit is in the same area as the
upper thermostat and must be reset manually when it operates.
BECAUSE THE HIGH LIMIT OPERATES ONLY WHEN
ABNORMALLY HIGH WATER TEMPERATURES ARE PRESENT, IT
IS IMPORTANT THAT A QUALIFIED SERVICE AGENT BE CONTACTED
TO DETERMINE THE REASON FOR OPERATION BEFORE RESETTING.

Turn “OFF” the heater electrical supply. Do not attempt to reset
thermostat with power on.

Remove the two screws securing the outer door and remove door.

Remove the insulation block and pad to expose the reset button
opening.

Reset the high limit by pushing in the red button marked “RESET”.

Replace the insulation block and pad so that it completely covers
the thermostat and element.

Replace the outer door.

Turn “ON” electric power to the water heater.

FOR YOUR INFORMATION

Summary of Contents for 184748-001

Page 1: ...RECTEDTOTHELOCALDEALERFROMWHOMTHEWATERHEATERWAS PURCHASED IFYOUAREUNSUCCESSFUL PLEASEWRITETOTHECOMPANYLISTEDONTHERATINGPLATEONTHEWATERHEATER GAMA certification applies to all residential electric water heaters with capacities of 20 to 120 gallons Input rating of 12 Kw or less Instruction Manual RESIDENTIAL HUD SIDE PLUMBING ELECTRIC WATER HEATERS FOR POTABLE WATER HEATING ONLY NOT SUITABLE FOR SPA...

Page 2: ...al Code and applicable local electrical and plumbing codes and tools necessary to confirm proper installation and operation of the water heater as they relate to the installation of electric water heaters The qualified installer must have a thorough understanding of the water heater Instruction Manual Service Agency A service agency also must have ability equivalent to a licensed tradesman in the ...

Page 3: ...3 GENERAL SAFETY ...

Page 4: ...r whose name appears on the rating plate 4 Carefully plan the place where you are going to put the water heater INSTALLATIONORSERVICEOFTHISWATERHEATERREQUIRES ABILITYEQUIVALENTTOTHATOFALICENSEDTRADESMAN IN THEFIELDINVOLVED PLUMBINGANDELECTRICALWORKARE REQUIRED Examine the location to ensure the water heater complies with the Facts to ConsiderAbout the Location section in this manual 5 For Californ...

Page 5: ... COLD WATER INLET LINE AS REQUIRED BY LOCAL CODES INSTALL SUITABLE DRAIN PANS UNDER HEATERS TO PREVENT DAMAGE DUE TO LEAKAGE REFER TO WATER HEATER LOCATION ON PAGE 8 INSTALLTHERMALEXPANSIONTANK OR DEVICE IF WATER HEATER IS INSTALLED IN A CLOSED WATER SYSTEM ...

Page 6: ...xing valves are available local plumbing contractor Consult a Qualified Installer or Service Agency Follow mixing valve manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat read the Temperature Regulation section in this manual LOCATING THE NEW WATER HEATER FACTS TO CONSIDERABOUT THE LOCATION Carefully choose an indoor location for the ne...

Page 7: ...n blanket unnecessary Should you choose to apply an insulation blanket to this heater you should follow these instructions below Failure to follow these instructions can result in fire serious personal injury or death Do not cover the temperature and pressure relief T P valve with an insulation blanket Do not cover the instruction manual Keep it on the side of the water heater or nearby for future...

Page 8: ...e water heater The water heater is equipped with 3 4 inch NPT water connections NOTE If using copper tubing solder tubing to an adapter before attaching the adapter to the cold water inlet connection Do not solder the cold water supply line directly to the cold water inlet it will harm the dip tube and damage the tank FIGURE 3 WATER PIPING PRESSURE TEST This section is only for the manufacturer in...

Page 9: ...lief valve and the tank Do not connect tubing directly to discharge drain unless a 6 inch air gap is provided To prevent bodily injury hazard to life or property damage the relief valve must be allowed to discharge water in quantities should circumstances demand If the discharge pipe is not connected to a drain or other suitable means the water flow may cause property damage The Discharge Pipe Sha...

Page 10: ...ucet Allow water to run until a constant flow is obtained This will let air out of the water heater and the piping 4 Check all water piping and connections for leaks Repair as needed T P VALVE and PIPE INSULATION On Selected Models Remove insulation for T P Valve and pipe connections from carton Fit pipe insulation over the incoming cold water line and the hot water line Make sure that the insulat...

Page 11: ...11 WIRING DIAGRAMS TURN OFF THE HEATER ELECTRICAL SUPPLY BEFORE SERVICING ANY ELECTRICAL COMPONENTS FIGURE 7 ...

Page 12: ...power when working on the water heater This could be with a circuit breaker or fuse block in the entrance box or a separate disconnect switch 2 Install and connect a circuit directly from the main fuse or circuit breaker box This circuit must be the right size and have its own fuse or circuit breaker 3 If metal conduit is used for the grounding conductor A The grounding electrode conductor shall b...

Page 13: ...ople are more likely to be permanently injured by hot water than others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap then you must take special precautions In addition to using the lowest possibl...

Page 14: ...armless bacteria is nontoxic to humans D An excess of active hydrogen in the tank This is caused by the corrosion protective action of the anode Smelly water may be eliminated or reduced in some water heater models by replacing the anode s with one of less active material and then chlorinating the water heater tank and all hot water lines Contact the local water heater supplier or service agency f...

Page 15: ...terminate to an adequate drain 6 Close the drain valve 7 Follow the instructions in the Filling the Water Heater section THERMOSTAT REMOVAL REPLACEMENT ANODE ROD INSPECTION The anode rod is used to protect the tank from corrosion Most hot water tanks are equipped with an anode rod The submerged rod sacrifices itself to protect the tank Instead of corroding the tank water ions attack and eat away t...

Page 16: ...against the tank 8 Attach the wires to the new thermostat NOTE Some of the terminals may require straight in wiring through an eye opening If wires are now looped recut and strip wire 3 8 to a straight length and insert 9 Put plastic terminal cover back in place 10 Replace the insulation block and pad to cover the thermostat 11 Replace outer door then turn the electric power ON ELEMENT CLEANING RE...

Page 17: ... terminal cover from the thermostat The terminal cover can now be removed from the thermostat FIGURE 18 7 Disconnect the two wires on the element and unscrew the old element from the tank FIGURE 19 8 Clean the area around the element opening Remove any sediment from or around the element opening and inside the tank 9 If you are cleaning the element you have removed do so by scraping or soaking in ...

Page 18: ...re the thermostat remains firmly against the surface of the tank FIGURE 21 16 Replace terminal cover on thermostat making sure the locking tabs on the terminal cover are in place 17 Replacetheinsulationblockandpadsothatitcoversthethermostat and element see Figure 21 18 Replace outer door 19 Turn ON electric power to water heater FIGURE 22 DRAIN VALVE WASHER REPLACEMENT See Figure 23 1 Follow Drain...

Page 19: ...ions and remove element Reposition or replace gasket on element Place element into opening and tighten securely Then follow Filling the Water Heater instructions in the Installing the New Water Heater section F Water from a drain valve may be due to the valve being slightly opened G The drain valve may be leaking at the tank fitting H Water in the water heater bottom or on the floor may be from co...

Page 20: ...iances near water heater Install thermal expansion tank DO NOT plug T P valve Check relief valve for proper operation DO NOT plug T P valve Drain and flush heater thoroughly then refill Chlorinate water supply Turn disconnect switch on or contact electrician Refer to temperature regulation Reduce hot water use Allow more time for heater to reheat water Have plumber check and repair leaks Contact d...

Page 21: ...ed accordingly The model number of your Water Heater will be found on the rating plate located above or adjacent to outer door Key No Part Description 1 Temperature Pressure Relief Valve 2 Outlet Nipple Assembly 3 Inlet Nipple 4 Conduit Bracket 5 Junction Box Cover 6 Upper and Lower Element 7 Element Gasket 8 Thermostat Bracket ea 9 Lower Thermostat 2 Pole 10 Terminal Cover 11 Lower Thermostat w H...

Page 22: ...22 NOTES ...

Page 23: ...23 NOTES ...

Page 24: ...24 ...

Reviews: