D2543-01-02 CN5219 SEM1000 Web User Guide 

 
 
 
 
The SEM1000 isolator is designed to be series connected into a new or existing (4 to 20) mA current 
loop and provide an isolated (4 to 20) mA signal capable of driving into 300 R. The output is powered 
from the input loop. 
 
 
 
 
 
 
 
 
Type 

 

 

Current input 2 wire loop powered 

Range 

 

 

(4 to 20) mA (30 mA maximum) 

Protection 

 

Reverse connection 

Voltage Drop 

 

5.5 V + O/P V Drop (O/P V Drop = O/P load x 0.02) 

Max Loop Supply 

 

35 V 

 
 
 
 
 
Type 

 

 

(4 to 20) mA source (Powered from input) 

Load 

 

 

(0 to 300) 

 (Open circuit limits at approximately 15 V) 

 
 
 
 
 

Isolation 

500 VAC (flash tested @ 1 kV) (Isolation method, opto-
coupler/transformer) 

Electrical Safety 

 

BS EN61010-1 Pollution Degree 2; Installation CAT II; CLASS I 

Ambient   

 

(0 to 70) ºC; (10 to 95) % RH non condensing 

Accuracy   

 

0.05 % full range output 

Stability   

 

0.01 % / ºC 

Response Time 

 

Less than 100 ms to reach 63 % of final value. 

EMC 

 

 

Compliant with BS EN50081-1, BS EN50082-1 

Connection 

 

Captive clamp screws 

Cable Size 

 

Maximum 4 mm² solid/2.5 mm² stranded 

Case Material 

 

Grey Polyamide 

Flammability 

 

To UL94-VO VDE 0304 Part 3, Level IIIA 

Dimensions 

 

(60 x 60 x 12.5) mm (67.5 mm above rail) 

Mounting   

 

Snap on "Top Hat" rail (DIN EN 50022-35) 

Adjustments 

 

Zero and Span Adjustment 

 
 
 
 
 
 
 

Page 1 

 
 
 
 
 
 
This unit must be housed within a suitable enclosure that will provide protection from the external  
environment, ensuring that the stated temperature and humidity operating ranges are not exceeded. It 
is good practice to mount the unit away from sources of electrical noise, such as switch gear and  
transformers. The unit enclosure is designed to snap fit onto a standard "Top Hat" DIN rail. To 
remove from rail, apply pressure at the bottom face at the back upwards towards the rail to release 
the spring clip and tip away from the top. The unit may be mounted in any orientation and stacked 
side by side along the rail. 
 
 
 
 
Connections to the isolator are made via screw terminals. Wire protector plates are provided inside 
each terminal. To maintain CE compliance twisted pair (screened) cables are recommended. It is also 
good practice to ensure that all (4 to 20) mA loops are grounded at a single point in the loop. Before 
installation, care must be taken to ensure enough voltage is available in the loop to drive the total loop 
load. Refer to the specifications listed for the voltage drop. In the case of the SEM1000 the additional 
voltage drop of the load connected in the isolated circuit, will be added to the loop drop of the isolator, 
for example a SEM1000 isolator driving into a 250 

 load will have a total loop drop of 10.5 V 

maximum. 
 
Refer to the SEM1000 series data sheet for further information on applications of this series of 
isolators. Please note the isolation provided by this device is only suitable for providing isolation  
between two process signals and therefore must not be used to provide isolation from hazardous 
voltages, such as mains supplies. 
 
 
 

Figure 1 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Page 2 

1.0 DESCRIPTION 

2.0 SPECIFICATION 

2.1 INPUT 

2.2 OUTPUT 

2. 3 GENERAL SPECIFICATION @ 20 °C 

3.0 INSTALLATION 

3.1 MECHANICAL 

3.2 ELECTRICAL 

SEM1000

ZERO

SPAN

OUT

IN