STATUS SCIENTIFIC CONTROLS
Installation, Commissioning & Routine Gas Testing
FGD10B Pellistor Gas Detector
TD18/008
Issue:
10
Change Note:
1904
Page 36
Step 5
Undo the circlip that retains the sensor in its housing. And replace the
sensor.
Step 6
Apply Loctite 243 or a compound equal strength to the threads Insert the
sensor housing into the FGD10B enclosure using the insertion tool.
Loctite