background image

Installation G 

Solar Tube Company - Eco Airpump 
www.ecoairpump.co.uk 
Support Line: 08444 930099 

11 

Filling the Resol Flowcon S 

 

NOTE! To be carried out when the system is cold or prior to the installation of the heat pipes 

 

1. 

Connect the brass hose adaptors to the fill connector (top on right hand side) and to the 
drain/flush connector (bottom on right hand side beside flowmeter) 

 
2. 

Connect the fluid (Tyfocor or similar) supply hose to the fill connector and open the valve 
beside it. The fluid supply hose can come from a Resol Proficenter pump, PAW canister 
pump, central-heating filling pump or a good quality pump-up garden sprayer. 

 
3. 

Connect the drain/flush hose to the drain/flush connector and open the valve beside it. 
Ensure the end of the hose lies in a container to capture the fluid, which will come out during 
the filling process. 

 
4. 

Close the ball valve at the top of the flowmeter by turning the slot of the screw to a horizontal 
position. Open the non-return valve (immediately above the pump) by using a 14mm spanner 
to turn the valve 45

 

(from 12 o’clock to 1h30m). 

 
5. 

Pump fluid into the system through the supply hose. Keep pumping after it comes out of the 
drain/flush hose until the fluid being released no longer has any bubbles in it. Fluid can be 
transferred from the drain/flush container to the pump container periodically. Typically, flush 
through the system for 15 minutes. It is necessary to open the valve on the flowmeter from 
time to time. 

 
6. 

Increase the pressure (on the pump station gauge) as much as the pump will allow 

to a 

maximum of 6 Bar 

by closing the drain/flush valve and pumping in some more fluid. If the 

pressure drops then there is a leak in the system. 

 
7. 

Open the valve on the flowmeter. 

 
8. 

Vent the pump using the screw in the middle of it (use large flat headed screwdriver).  

 
9. 

Reduce pressure by releasing a little fluid from the drain/flush valve to the collector 
manufacturer’s recommended operating pressure (typically 1.25 Bar when system is cold for 
STC collectors). 

 
10. 

Run pump at 100% speed (using manual control 

– see controller instructions) for about 15 

minutes. Stop pump and open manual bleed valve to release any remaining air. 

 
11. 

Restart pump via controller at 100%. Adjust speed by turning black knob on pump (I, II, III) so 
that reading on lower edge of float in flowmeter reading is the same or slightly higher than 
collector optimum speed (0.1L/min for STC collectors, e.g. 2L/min for each 20 tube collector). 
The flow rate can be adjusted via the valve on the flowmeter. 

 
12. 

Open the ball valve above the pump by turning it back to 12 o’clock. 

 
13. 

Fit the front insulation jacket to the pump station and switch the controller to automatic 
operation.

 

 

NB. The Flowcon S can usually be bled by releasing air from the pump and manual air separator. Some 
systems may need to be manually bled at their highest point. 

Summary of Contents for Solar SPA Collector Kit

Page 1: ...any persons working with you are competent to do so and only after you have assessed all risks and either eliminated them or reduced them to safe levels Caution There is a boiling risk which is fully...

Page 2: ...are here to help so please let us know if you are having problems or require some more clarification Just in case you need reminding why you chose a STC System here are the key features of our kits 1...

Page 3: ...models will perform well even when not pointing due south However it will be necessary to increase the number of tubes over what would be expected for a due south installation Position Allow extra eva...

Page 4: ...frame vertical pieces to back of manifold 2 Turn over 3 Attach cross rail so that opened groove is at top 4 Secure cross rails using M13 bolts and stainless fittings 5 The collector can now be offere...

Page 5: ...lts 2 Attach feet folding in tabs to fit M10 X 45 bolts 3 Attach side supports M13 x 20 bolts 4 Attach rear supports M13 x 20 bolts 5 Join rear supports at middle of X M10 x 30 bolt 6 The collector ca...

Page 6: ...s to line up with the holes that are not in line with the rafters you will see the holes very clearly 3 Back on the roof drill pilot holes into the wood drilling through your holes in the tiles using...

Page 7: ...mm brass fittings or 22mm T brass fittings if an external air vent is fitted In all cases a hole must be cut in the tiles at each end of the collector or at each end of a multiple collector array The...

Page 8: ...t is attached to the fitting WITHOUT the washer and tightened this creates a flange on the end of the pipe 4 Unscrew the fitting insert the washer reconnect the fitting and tighten The compression fit...

Page 9: ...emperature sensor provided with the controller from the pump station box smear some heat transfer paste from the tube in the small white box found in the collector frame box onto the metal sensor tube...

Page 10: ...rubber seal facing towards the pump station Connect the flow DN16 2 in 2 pipe the one carrying the heated fluid from the collector to the inlet upper of the water cylinder s solar coil Connect the out...

Page 11: ...ner periodically Typically flush through the system for 15 minutes It is necessary to open the valve on the flowmeter from time to time 6 Increase the pressure on the pump station gauge as much as the...

Page 12: ...tips of the heat pipes Next Put rubber end caps on tube it is often easier to wipe a little washing up liquid around the top and the bottom ends of the glass tubes to ease fitting Push copper tip of...

Reviews: