background image

Installation G 

Solar Tube Company - Eco Airpump 
www.ecoairpump.co.uk 
Support Line: 08444 930099 

Using Leaded Roof Grommets and Pre-Insulated Flexible Stainless Steel Pipe 

 

 

 

The size of the hole is less important when using leaded roof grommets because they provide 
their own weatherproof seal. They can be used instead of the tile beneath them. In which case, 
simply lay the leaded tile in the gap left by the replaced roof tile, making sure that the top edge 
lies under the tile immediately above it and the bottom edge lies on top of the tile immediately 
below it 

– to keep the rain out. 

 
 Typically, holes of 60-80mm diameter are cut using a ceramic hole cutter, centres of the holes 
should be 100mm from the ends of the 22mm copper tails. The holes should be slightly below 
the tails in order to prevent air locks. If using a Flowcon S pump station; an exterior air vent is 
not usually necessary. 
 
The leaded roof grommet is then placed over the tile and trimmed to fit, ensuring that it lies 
under the lower edge of the tile immediately above it. The rubber grommets should be cut 
between the second and third ridge leaving a hole through which the pipe can be fed (including 
its insulation). 
 
Remove the black (high temperature) sensor provided with the controller from the pump station 
box, smear some heat transfer paste (from the tube in the small white box found in the collector 
frame box) onto the metal sensor tube and push into the sensor pocket. The sensor pocket will 
accept many types of sensor so try not to push the Resol sensor in too far 

– the whole sensor 

tube should be inside the manifold with the end just inside the rubber grommet.  
 
The sensor wire can now go through the small lump beside the main part of the lead roof 
grommet and be joined on to the blue sensor wire. 
 

NB. The fluid flows from the left of the collector to the right as viewed from the front. This 
is because the sensor pocket is on the right side of the collector i.e. the heat reading is 
taken as the water leaves the collector. 

It is recommended that the sensor wire be joined inside the roof void. Therefore, cut the 
insulation of the pipe containing the blue sensor cable about 1 metre before the cut end. Pull the 
blue sensor wire out. 
 
The DN16 2-in2 pipe is then fed from inside the roof void through the 2 holes. Use back nuts 
and compression fittings to connect to manifold. Stretch insulation over fittings. 
 
Connect the sensor wire to the blue cable then run the DN16 pipe down to the pump station, 
taking care to avoid any high points that could lead to air locks. The pipe is usually held in place 
using our brackets or thick cable ties.

 

 

Summary of Contents for Solar SPA Collector Kit

Page 1: ...any persons working with you are competent to do so and only after you have assessed all risks and either eliminated them or reduced them to safe levels Caution There is a boiling risk which is fully...

Page 2: ...are here to help so please let us know if you are having problems or require some more clarification Just in case you need reminding why you chose a STC System here are the key features of our kits 1...

Page 3: ...models will perform well even when not pointing due south However it will be necessary to increase the number of tubes over what would be expected for a due south installation Position Allow extra eva...

Page 4: ...frame vertical pieces to back of manifold 2 Turn over 3 Attach cross rail so that opened groove is at top 4 Secure cross rails using M13 bolts and stainless fittings 5 The collector can now be offere...

Page 5: ...lts 2 Attach feet folding in tabs to fit M10 X 45 bolts 3 Attach side supports M13 x 20 bolts 4 Attach rear supports M13 x 20 bolts 5 Join rear supports at middle of X M10 x 30 bolt 6 The collector ca...

Page 6: ...s to line up with the holes that are not in line with the rafters you will see the holes very clearly 3 Back on the roof drill pilot holes into the wood drilling through your holes in the tiles using...

Page 7: ...mm brass fittings or 22mm T brass fittings if an external air vent is fitted In all cases a hole must be cut in the tiles at each end of the collector or at each end of a multiple collector array The...

Page 8: ...t is attached to the fitting WITHOUT the washer and tightened this creates a flange on the end of the pipe 4 Unscrew the fitting insert the washer reconnect the fitting and tighten The compression fit...

Page 9: ...emperature sensor provided with the controller from the pump station box smear some heat transfer paste from the tube in the small white box found in the collector frame box onto the metal sensor tube...

Page 10: ...rubber seal facing towards the pump station Connect the flow DN16 2 in 2 pipe the one carrying the heated fluid from the collector to the inlet upper of the water cylinder s solar coil Connect the out...

Page 11: ...ner periodically Typically flush through the system for 15 minutes It is necessary to open the valve on the flowmeter from time to time 6 Increase the pressure on the pump station gauge as much as the...

Page 12: ...tips of the heat pipes Next Put rubber end caps on tube it is often easier to wipe a little washing up liquid around the top and the bottom ends of the glass tubes to ease fitting Push copper tip of...

Reviews: