I N S T A L L A T I O N
12
Installation – step 1
IER Positioning & Mounting
General guidelines for positioning
IER
electric steam humidifier should be positioned so that:
Length of the steam line (or hose) is as short as possible,
In case steam hose is used, the bend radius of 12in (300mm) is ensured
Humidifier is easily accessible for service
CAUTION. Risk of malfunction due to vibration. Do Not mount IER
electric steam
humidifier directly on ventilation duct
.
CAUTION. Risk of flooding.
Ensure that the local where
IER
electric steam humidifier
will be installed is equipped
with floor drain.
In case of no floor drain is available; installation of a water leak detector is required in order to
prevent any flooding in case of abnormal operation or service.
IER
electric steam humidifier should be installed in a well-ventilated and dry environment.
If local is subject to below freezing point temperature, activation of ant freezing function of the
IER
electric steam humidifier is required.
For outdoor installation please contact your steamOvap representative to order and install
special outdoor optional enclosure for IER.
IER
maximum ambient conditions:
Temperature: 41°F to 122°F [+5 to +50°C]
Relative Humidity: 90%RH max (non condensing)
Ingress Protection for
IER
standard enclosure: IP20