I N S T A L L A T I O N
14
Clearances for IER with space blower
Figure 7 – minimum clearances for SB
Clearance guidelines
There is no minimum clearance on both side of the Space blower, but it is a good practice to
have a clearance of 4 to 8 in [100 to 200mm] for ease of installation and service
Front clearance of 80in [2000mm] is required for steam absorption.
A top clearance is required of 24in [600mm] for access and for steam absorption to avoid any
condensing on the ceiling.