I N S T A L L A T I O N
General guidelines for Mounting
CAUTION. Risk of malfunc on. IER
electric steam humidifier must be levelled
in X & Z axis.
Installa on on wall (without moun ng bracket)
1. Verify that wall structure and strength is appropriate to support the opera ng weight
of the IER electric steam humidifier.
In case, the wall is not solid enough to support opera ng weight of
IER
electric steam
humidifier, install humidifier on the floor stand (
FS
op on is available to your
steamOvap representa ve).
2. Mark the wall or support according to the above holes loca on, and drill 4 holes to the
wall or support as per the size of anchors and/or screws.
3. Use anchors of sufficient size (at least 1/4in [6mm]). Insert those anchors and the 2 top
screws, ensure that the screw heads extends 1/4in [6mm] from the wall, so that the
IER
electric steam humidifier will be able to be hung on those 2 screws.
4. With front cover removed, hung the
IER
electric steam humidifier onto the 2 top
screws.
Insert the bo om screw through the back plate of the humidifier and into the anchors
in the wall.
Ensure that the humidifier is properly levelled.
Tighten the 3 screws. Re verify the level in the 2 direc on X and Z axis.
5. Re-install the front cover to the humidifier.
6. Op onal Moun ng bracket (op on
MB
) is available to your steamOvap representa ve
in order to ease up wall moun ng process.
16