background image

Torque Adjustment

Brake is factory set for nominal rated static 

torque which is maximum torque. Torque 

may be decreased up to 50% for increased 

stopping times up to 2 second stop time. 

The torque on the 1-1/2 lb-ft brake may not 

be reduced.
Turn both spring adjustment screws (11), 

Figure 3, equal amounts counterclockwise 

to decrease torque. See Table A for torque 

reduction permissible amounts.

11

11

10

10

Figure 3

 Nominal  Original  Maximum  % Torque 

 Static  Spring  Counter-  Reduction 

 Torque  Height  clockwise 

per 

 (lb-ft)  (inches)  Turns 

Turn

  1-1/2 

1.56” 

 - 

-

 3 

1.50” 

 

 6 

1.47” 

 

 10 

1.53” 

7%

 15 

1.53”

 20 

1.53”

 25 

1.47”

TABLE A

COIL FAILURE

SUPPLY VOLTAGE CAUSE

SUPPLY VOLTAGE CORRECTION

Line voltage >110% of coil rating  Reduce voltage or replace with prop-

er rated coil

AC input on a DC coil 

Replace rectifier or replace with 

proper rated coil.

Excessive voltage drop during 

inrush time

Increase current rating of power 

supply.

WIRING CAUSE

WIRING CORRECTION

Leadwires interfering with plunger 

pull-in

Reroute wiring away from plunger 

and other moving components.

Excessive voltage drop during 

inrush time

Increase leadwires size from power 

supply

Coil leadwire shorted to ground 

Replace coil or leadwire and protect 

with wire sleeving

SOLENOID ASSEMBLY CAUSE

SOLENOID ASSEMBLY  

CORRECTION

Plunger not seating flush against  

solenoid frame 

Loosen solenoid mounting screws 

and reposition frame to allow full 

face contact

Plunger cocked in coil preventing 

pull-in

Realign solenoid frame 

Excessive solenoid/plunger wear 

at mating surface

Replace solenoid assembly 

Broken shading coils

Replace solenoid assembly

WORN PARTS CAUSE

WORN PARTS CORRECTION

Excessive wear of solenoid link 

arm and/or shoulder bolt 

Replace link arm and link bolt; also 

inspect plunger thru-hole for  

elongation

Plunger guides worn down and 

interfering with plunger  

movement

Replace guides 

 

APPLICATION CAUSE

APPLICATION CORRECTION

Machinery cycle rate is exceeding 

brake rating

Reduce brake cycle rate or use alter-

nate control method

High ambient temperature 

(>110%) and thermal load 

exceeding coil insulation rating

Use Class H rated coil and /or find 

alternate method of cooling brake 

Brake coil wired with windings of 

an Inverter motor or other  

voltage/current limiting device

Wire coil to dedicated power source 

with instantaneous coil rated voltage 

MISCELLANEOUS CAUSE

MISCELLANEOUS CORRECTION

Wrong or over tightened torque 

Replace with proper spring or refer 

to Installation section for proper 

spring height

Excessive air gap

Reset, refer to Installation Section 4

EXCESSIVE WEAR / OVERHEATING

AIR GAP CAUSE

AIR GAP CORRECTION

Low solenoid air gap 

Reset air gap (refer to Air Gap 

Adjustment)

Disc pack dragging 

 

Inspect endplate, hub and discs for 

dirt, burrs, wiring and other sources 

of interference preventing disc “float”

CYCLE RATE CAUSE

CYCLE RATE CORRECTION

Brake “jogging” exceeding coil 

cycle rate

Reduce cycle rate or consider alter-

nate control method

Thermal capacity is being  

exceeded

Reduce cycle rate, use alternate 

control method or increase brake 

size

ALIGNMENT CAUSE

ALIGNMENT CORRECTION

Broke endplate not concentric to  

motor C-Face 

Motor register must be within  

.004” on concentricity;  

Motor shaft runout is excessive 

Must be within .002”; runout;  

consult motor manufacturer

Brake is being operated on a 

incline greater than 15° above or 

below horizontal

Vertical separator springs must be 

used to prevent discs from  

becoming cocked

WORN PARTS CAUSE

WORN PARTS CORRECTION

Friction disc excessively worn  

(disc can wear to 1/2 original  

thickness or .093”)

Replace friction discs.

Endplate, stationary disc or  

pressure plate warped

Replace warped or worn component 

Linkages and/or pivot pins worn

Replace all worn components

Motor shaft endfloat excessive 

Endfloat must not exceed .020”; con-

sult motor manufacturer

HUB CAUSE

HUB CORRECTION

Burr on hub interfering with disc 

“float”

File off burr 

Set screw backed out and  

interfering with disc

Retighten set screw; use Loctite® 

242 to help secure

MISCELLANEOUS

MISCELLANEOUS

Solenoid plunger not pulling  

completely 

Check line voltage (±10% of  

nameplate rating) or replace worn 

solenoid assembly

Wiring is restricting disc pack 

movement

Reroute wiring 

Excessive stop time  

(2 seconds or greater)

Increase brake size/torque or use 

alternate control method

High Ambient temperature  

(in excess of 110°F)

Reduce cycle rate or use alternate 

method of cooling

TROUBLESHOOTING

Rexnord Industries, LLC, Stearns Division, 5150 S. International Dr., Cudahy, WI 53110, (414) 272-1100 Fax: (414) 277-4364  www.stearnsbrakes.com 

TORQUE ADJUSTMENT 

Summary of Contents for 1-056-700 Series

Page 1: ...k or a respirator while removing dust from the inside of a brake b Use a vacuum cleaner or a soft brush to remove dust from the brake When brushing avoid caus ing the dust to become airborne Collect the dust in a container such as a bag which can be sealed off 10 Caution While the brake is equipped with a manual release to allow manual shaft rotation the motor should not be run with the manual rel...

Page 2: ...1 3 clockwise For brakes with vertical sprngs see Figure 5A or 5C FRICTION DISC REPLACEMENT SERIES 1 056 700 2 Note Friction discs can wear to 1 2 their original thicknes or 093 A Remove housing nuts and slide tie bolt out of brake B Remove housing from endplate 4 For vertical assembly of 20 25 lb ft brakes refer to page 3 Slide endplate over hub noting position of stabilizer clips if used Refer t...

Page 3: ...stationary disc hole Springs are inserted from the side opposite the indent mark see Figure 2B Stationary disc should be placed on a clean flat surface with a clearance hole to allow the tip of the spring to extend through the bottom side of the sta tionary plate Using the 1 8 pin pro vided and a hammer drive the spring until the large coil diameter bottoms out against the disc Reassemble the disc...

Page 4: ...ndings of an Inverter motor or other voltage current limiting device Wire coil to dedicated power source with instantaneous coil rated voltage MISCELLANEOUS CAUSE MISCELLANEOUS CORRECTION Wrong or over tightened torque Replace with proper spring or refer to Installation section for proper spring height Excessive air gap Reset refer to Installation Section 4 EXCESSIVE WEAR OVERHEATING AIR GAP CAUSE...

Reviews: