Failure analysis 
PF166 

 

 

  Pfad \ Datei: 

I:\Projekte\SOLAR\PV-Entw\FREEZER\_E5970_KS-solar-LHG\14_Service\Failure analysis.doc 

Seite 1 von 5   

  Speicherdatum: 

 

Bearbeiter:   Gutzeit 

 

 

The PF166 is running with extra low voltage. There is no risk during maintenance and testing 
by  high  voltage.  Nevertheless  use  isolated  tools  and  a  fuse  in  the  battery  cable  to  protect  a 
short circuit of the battery. Please prevent as well ESD. 

 

1.

 

Check installation

 

 

Please  check  if  the  display  shows  any  number  or  if  the  Minus-LED  is 
blinking 

[40]

. If no display appears check battery connection: 

 

polarity 

 

broken fuse 

 

damaged cable or connector 

2.

 

Battery voltage

  

Please  check if the battery voltage is higher than the cut-off voltage of the  compressor. If 
the battery voltage is below 10,4V or in between 17,0V and 22,8V the inverter box 

[235]

 is 

disconnecting the compressor to protect the battery against deep discharge. So voltage had 
to  be  between  10,4V  and  17,0V  in  a  12V  system  or  between  22,8V  and  30,5V  in  a  24V 
system.   
The display 

[90] 

is already operating if the compressor 

[230]

 is disconnected by the inverter 

box 

[235]

.  If  the  battery  voltage  is  lower  than  the  cut-of  level,  the  LED  connected  to  the 

inverter box (between "+" and "D", see topic 5) is flashing one time.   
After recharging the battery the compressor 

[230] 

will start automatically after reaching the 

cut-in voltage. 

 

Cut-off 

Cut-in 

12V battery 

10,4V 

11,7V 

24V battery 

22,8V 

24,2 

°C

°C

°F

°F

electronic 
thermostat with 
user interface 
GTC 

inverterbox with 
speed control 
101N0300 