background image

 

19 

 

 
 

Accumulator tank capacity 

 
 

NOTE: 

The heat can be supplied for example 

by an accumulator tank. The following applies 
as a reference for the minimum storage boiler 
content: 

 
 
 
 
 
         :  Accumulator tank capacity in L 
 
         :  Nominal heat output in kW 
 
         :  Burning period in h 
 
         :  Heating load of the premises in kW 
 
         :  Minimum heat output in kW 
 

 
Heating  boilers  using  several  allowable  fuels 
should  have  the  tank  size  based  on  the  fuel 
that requires the largest accumulator tank. 
The accumulator tank is not necessary when 
the required volume is less than 300 l. 
 
 
 

Transportation and storage

 

 
The  manufacturer  handles  the  boiler  that  is 
on  a  palette  and  secured  against  shifting 
(with  screws).  The  boiler  may  not  be 
transported  in  a  different  position  than  on  its 
base. 
At  least  regular  storage  conditions  shall  be 
ensured 

during 

boiler 

storage 

and 

transportation (non - aggressive environment, 
air  humidity  lower  than      75  %,  temperature 
range from 5 °C to 55 °C, low dustiness and 
preventing influence of biological factors). 
The  force  may  not  be  applied  on  the  boiler 
coverings  and  panel  during  storage  and 
transportation. 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                             Fig. 08 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                            
 
 
 
 
 
 
 
 
 

                                                            Fig. 09 

Summary of Contents for ARTA series

Page 1: ...REV 01 2012 122088 ...

Page 2: ... of this installation and maintenance manual must be followed precisely If you require assistance or further information contact a qualified installer or an appropriate service provider The installation and service instructions are a component of the technical documentation and must be handed over to the operator of the heating system Discuss the instruction in this manual with the owner or operat...

Page 3: ...12 Overnight heating mode 13 Removing solid combustion residuals 13 Dewing and tarring 13 Boiler shutdown 13 Short term shutdown 13 Long term shutdown 14 Important information 14 Boiler repairs 14 Warranty and warranty conditions 14 Boiler delivery 14 Installation instructions 14 Boiler installation General information 14 Heating water requirements 15 Boiler Location 15 Minimum distance 16 Boiler ...

Page 4: ...4 Information on the boilerplate The boiler serial no is shown on the plate which is attached to the backside cover panel of the boiler body 20 26 35 43 ...

Page 5: ...5 Boiler dimensions ...

Page 6: ...6 Boiler packaging ...

Page 7: ...7 Technical parameters ...

Page 8: ...d appropriate user reaction to them with fundamental parts of the boiler and their controls If the same person who installs it delivers the boiler to the client he must make sure that the original packaging is available in case the boiler has to be transported again 7 Check the delivery for completeness 8 Check whether the model and type supplied is suitable for the required use 9 Whenever you are...

Page 9: ...Any interference by children persons under the influence of narcotic drugs certified persons etc when using the boiler must be prevented Operating Instructions ARTA Series Boiler General features ARTA series solid fuel fired boiler is designed for heating both residential and industrial buildings Besides professional installation precondition for correct functioning of the boiler is the required c...

Page 10: ...ulation Head 2 Arm holder 3 Arm 4 Regulator body 5 Hexagon 6 Pit When fitting the safety and the control elements remember to meet the principles of work safety If replacing of safety device and of thermo mechanical regulator is necessary please use recommended devices in case of using any other type of the device negotiate with Honeywell Functionality of thermo mechanical output regulator must be...

Page 11: ...ctioning of the heating controls Please note The service technician must show the user how to control the boiler and enter the date when the boiler was put into service into the warranty certificate Filling up and draining the heating system The system can only been filled up or topped up with water which meets the parameters specified by EN standards The water must be clear colourless free of sus...

Page 12: ...ally the secondary air supply rosette in the stoking door When the flame turns yellow shut the secondary air supply rosette again When the boiler has reached the required output it is suitable to partially shut the flue thrust flap to prevent heat from unnecessarily escaping into the chimney Do not start the boiler without connecting the boiler to the chimney Control chimney connections before sta...

Page 13: ...stion chamber from underneath the stoker Dewing and tarring When starting fire in a cold boiler water condensates on the walls and runs down into the ash compartment which may make an impression that the boiler is leaking This dewing will disappear after the astray has settled on the boilers inside walls When running the boiler with low water temperature usually below 65 C or when using damp fuel ...

Page 14: ...acements of some parts e g sealing cords Please note When repairing the boiler original parts must always be used Warranty and warranty conditions ARTA boilers are covered by warranty specified in the warranty certificate Service book and user and Installation guide chapter Introduction Installing the boiler Boiler delivery ARTA series boilers are supplied completely assembled and functionally tes...

Page 15: ... diagrams By Pass line s valve must be kept closed as the boiler is working normally By Pass line s valve can be used in electricity problems and must be opened if there is a risk of overheating in system water caused by an electricity cut or problem The pipe used in by pass line must be at least in the diameter of plumbing systems pipe UPS Power Supply Units can be used for preventing electricity...

Page 16: ... a room other than the one in which the boiler is installed Minimum distance Fig 05 Do not put flammable materials on top of the boiler or near the boiler than specified safety distance Boiler room disposition layout Illustrates minimum distances which must be kept in order to ensure safe operation of the boiler room and allow manipulations with the boiler such as cleaning and stoking The distance...

Page 17: ...ode regulations manufacture s instructions and in consultation with an approved flue installer The boiler may only be connected to a flue gas system with proper flue draft technical spec table The dimension calculations of the flue gas path must be based on the flue gas mass flow rate at maximum rated output The effective chimney flue height is measured from the point of entry of the flue pipe int...

Page 18: ...mmable materials for the flue gas system The figures in tab are only guide figures The draft depends on the diameter height roughness of the chimney wall and the temperature difference between combustion products and the outside atmosphere We recommend the use of a chimney liner Have precise calculations carried out by a heating engineer or flue installer Coefficient 0 041 for wood Coefficient 0 0...

Page 19: ...nk The accumulator tank is not necessary when the required volume is less than 300 l Transportation and storage The manufacturer handles the boiler that is on a palette and secured against shifting with screws The boiler may not be transported in a different position than on its base At least regular storage conditions shall be ensured during boiler storage and transportation non aggressive enviro...

Page 20: ...ne ash will depend on the quality of the fuel used and on the boiler operating conditions If the boiler is oversized or was for some reason run at low temperatures more soot is generated This may also result in inadequate chimney thrust Flue gas cleaning The boiler must be cleaned regularly at least once a week is with a steel brush Open the boiler upper cleaning door All boiler walls inside the c...

Page 21: ...The ashes must be removed from the combustion chamber ash pan every 1 3 days Fig 12 Open the ash pan door Remove the combustion residues from the ash pan with the ash shovel Do not place hot ashes in plastic and waste containers ...

Page 22: ...22 Hydraulic Connection Diagrams ...

Page 23: ...id fuel boiler is designed as a three pass Air inlets If the air vent is closed completely there is no complete combustion Creosote accumulates on the heating surfaces which requires more cleaning effort 1 Primary air inlet 2 Secondary air inlet Fig 14 ...

Page 24: ...24 ARTA boiler parts ...

Page 25: ...25 ARTA boiler spare parts lists ...

Page 26: ...26 ...

Page 27: ...27 Troubleshooting ...

Page 28: ...28 NOTES ...

Reviews: