background image

10

DIN

Deutsches Institut für Normung

VDE

Verband der Elektrotechnik

(German Institute for Standardisation)

Elektronik Informationstechnik e.V
(Association for Electrical,
Electronic & Information 
Technologies).

U

r

Rated voltage in volts (V)

I

r

Rated current in 
amperes (A)

Pr

Rated input power in watts (W)

CO

2

Carbon dioxide

ppm

parts per million 

α

Potentiometer setting angle 

m+NN

Metres above sea level in metres (m)

in degrees (°) 0° – 270°

Abbreviations and symbols used

The CO

2

air quality sensor described below

measures the concentration of carbon dioxide
(CO

2

) in room air by means of an optical two-

channel measurement system. 
The CO

2

air quality sensor uses an LED "traffic

light" display (green, amber, red) to indicate
when the quality of room air rises above or
falls below internally selected threshold values.
In addition, 3 beeps each lasting 1s sound
when changing from green to amber, and a
continuous audible signal lasting 5s sounds
when changing from amber to red.
When room air is fresh, you can compensate
for the effect of atmospheric pressure (weather
and / or altitude above sea level) simply by
pressing a button.

However, the air quality sensor is not intended
for use as a measuring device or as part of a
gas warning or other safety system. The sen-
sor is designed for operation in dry rooms at a
temperature of 5°C to +40°C and is protected
against medium-sized solid bodies by an IP20
rated enclosure for "surface" mounting. 

All work, such as assembly work, installation
and testing, must be carried out by skilled per-
sonnel. 

How it works

Locally applicable assembly and installation
provisions, guidelines and regulations must be
observed. In particular, this applies to:

VDE guidelines and regulations, 
e.g. DIN VDE 0100 

Guidelines and regulations issued by the in-
dustrial employers' liability insurance associ-
ations, e.g. accident prevention regulations
for electrical installations.

No liability can be accepted for improper appli-
cation, assembly and installation or for the use
of non-genuine accessory parts!

Regulations to be followed

11

Function

Range

Measuring range

300ppm – 2000 ppm CO

2

Accuracy

± 100 ppm (± weather-induced fluctuations of approx. 40 ppm)

Pressure range

In any weather and up to 2000m above sea level 
(manual altitude compensation)

Temperature (storage)

-40°C to +85°C

Temperature (operating)

5°C to   40°C

Response time (T90)

3 min

Sensor life

> 15 years

Rated input power 
Pr, Ir

2.8 W max. approx. 12mA at 240V ac; 50 – 60 Hz
2.3 W max. approx. 20mA at 110V ac; 50 – 60 Hz

Supply voltage Ur

110 – 240V, 50/60 Hz,
installation using screw terminals on the enclosure baseplate

Protection class 

II, doubly insulated

Type of enclosure 

IP 20

CO

2

air quality sensor

Room version (surface mounting). 

EMC conformity

DIN EN 61326-1:1997

Electrical safety

EN60335-1

Controls

- Potentiometer

Altitude calibration (m above sea level)
(the ppm threshold setting shown on the scale is not 
activated on the Aircheck "Signal" model)

- Button

for fresh-air calibration / altitude setting

Display

LED "traffic light" display

LED "traffic light" ("green" < 1000ppm; 
"amber" 1001 – 1500ppm; "red" > 1500ppm)

(3 visible LED’s in enclosure cap) 
colour changes at 200ppm below the above-stated 
incrementation thresholds to ensure that reliable colour 
transitions are achieved at the switching points.
(no beeping, no flashing LED)

Enclosure

ABS white

Technical specifications

One-time adjustment of air pressure in relation to altitude at the site of installation 
(0 to 2000 m above sea level).

BDAL_AirCheck FH_DE-GB  09.01.2006  14:41 Uhr  Seite 11

Summary of Contents for CO2-AirCheck Signal

Page 1: ...olera C Atenas 5 E 08191 Rubi Barcelona Tel 34 93 5 88 67 25 Fax 34 93 5 88 68 46 e mail saet94 retemail es P Pronodis Solu es Tecnol gicas Lda Rua do Caseiro no 87 A B Vilar P 3810 078 Aveiro Fon 351...

Page 2: ...durchgef hrt werden VDE 0100 Allgemeines Diese Betriebsanleitung enth lt aus Gr nden der bersichtlichkeit nicht s mtliche Detailin formationen zu allen Typen des Produkts und kann auch nicht jeden den...

Page 3: ...dete Abk rzungen und Symbole Einmalige Einstellung des von der Montageh he abh ngigen Luftdrucks 0 bis 2000 m NN Der nachfolgend beschriebene CO2 Luftg te sensor dient der Erfassung der Kohlendioxid C...

Page 4: ...des LED Ampel Displays ber die Taste Fresh Air Cal Die Schaltschwellen k nnen Sie auch nach eigenem Befinden subjektiv einstellen Hierf r drehen Sie das Potentiometer auf 0 Ist die Raumluft subjektiv...

Page 5: ...l details on all product models and are also unable to cover every conceivable case of installation operation or maintenance If you require further information or encounter problems that are not cover...

Page 6: ...particular this applies to VDE guidelines and regulations e g DIN VDE 0100 Guidelines and regulations issued by the in dustrial employers liability insurance associ ations e g accident prevention regu...

Page 7: ...fic light display using the Fresh Air Cal button You can also set the switching thresholds to suit your own perception subjectively To do this turn the potentiometer to 0 If you feel the air in the ro...

Reviews: