6

INSSFEU0914

hEATINg DEmAND, ECO mODE, W1 DEmAND (WITh FURNACE INTELLIgENCE)

100% Heat,

Med speed,

Adjust. limit

50% Heat, 

Low speed

Adjust. limit

5 MIN

30 MIN

35 MIN

MoDeS

The user can select two different heating modes by pressing the button located in the middle of the control panel (item #4 in the control panel 

picture). The two modes affect the heating demand and the functions when used with the heat pump and the STANDARD mode described previ-

ously. When ECO mode is selected, the heating sequence is longer than STANDARD and the heating power will ramp-up to 50% heating for five 

(5) minutes. If a heating demand lasts 30 minutes, a second sequence of five (5) minutes activates a ramp-up of the elements to 100% heating at 

medium speed.

hEATINg DEmAND, ECO mODE, W2 DEmAND (WITh FURNACE INTELLIgENCE)

100% Heat,

Med speed,

Adjust. limit

50% Heat, 

Low speed

Adjust. limit

5 MIN

10 MIN

15 MIN

Also, the temperature compensation option explained previously in installation type ”B” does not operate in ECO mode.Thus, whenever the heat 

pump is activated (Y demand), no electric heating will be supplied by the furnace.

For a two-stage thermostat, when the W2 is in demand, the furnace waits another five (5) minutes before ramping-up for five (5) minutes until 100% 

of heating capacity is reached.

Summary of Contents for 360 Comfort

Page 1: ...r information or to consult this guide online please visit our website at www stelpro com This unit complies with the CSA and UL standards This unit is approved according to the Canadian and American...

Page 2: ...electrical wiring of the unit Because this unit is hot when in use it may pose risks even in normal operation Therefore be careful and responsible when using it To avoid burns do not let bare skin tou...

Page 3: ...s up at medium speed and the furnace elements are activated one by one to reach the adjustable temperature limit set on the potentiometer of the furnace control card If there is still a W1 heating dem...

Page 4: ...thout any heating demand Moreover it will reactivate it when a new heating season begins Note that the pilot light indicating the heating option will blink if the furnace deactivates this option becau...

Page 5: ...ndicate which installation has been programmed The heat pump can operate all year and allows the user to make energy savings due to the plenum temperature regulation function exclusive to Stelpro This...

Page 6: ...ting power will ramp up to 50 heating for five 5 minutes If a heating demand lasts 30 minutes a second sequence of five 5 minutes activates a ramp up of the elements to 100 heating at medium speed Hea...

Page 7: ...specify the model of your furnace as well as its serial number Air filter Excessive dust or dirt accumulation can block the airflow forcing the unit to work harder to maintain the desired temperature...

Page 8: ...s turned on Faulty connections Voltage higher than that indicated on the nameplate Elements are on but the motor does not work Defective motor or condensator Faulty relay The desired room temperature...

Page 9: ...10 8 2 BLO 005 SQUIRREL CAGE BLOWER 12 11 3 MO 036 1 MOTOR 208 240 VAC 1PH 1 3HP 4 SPEEDS 1075 RPM 3 MO 037 MOTOR 208 240 VAC 1 PH 1 HP 3 SPEEDS 1075 RPM 3 MO 049 MOTOR 120VAC 1PH 1 3HP 4 SPEEDS 1075...

Page 10: ...ty or personal injury damages penalties special or punitive damages damages for lost profits loss of use of equipment cost of capital cost of substitute products facilities or services shutdowns slowd...

Reviews: