Installation and Operation Instructions 

 

 

 
 

NOTE: Read this entire instruction sheet before starting the installation.

  

     

        

I

MPORTANT 

C

ONSIDERATIONS

 

Improper  installation,  adjustment,  alteration,  service, 
maintenance,  or  use  can  cause  fire,  electrical  shock,  or 
other  conditions  which  may  cause  personal  injury  or 
property damage.  Consult your supplier or Steril-Aire for 
information or assistance.   
 
Understand  the  signal  words 

DANGER

WARNING

,  or 

CAUTION

.  These words are universally used for overall 

safety.   

DANGER 

identifies  the  most  serious  hazards 

which  will  result  in  severe  personal  injury  or  death.  

WARNING

  signifies  hazards  which  could  result  in 

personal  injury  or  death.   

CAUTION

  is  used  to  identify 

unsafe  practices  resulting  in  minor  personal  injury  or 
product and property damage.   
 
 

WARNING:    Before  performing  maintenance  or 

service  on  fixture,  ensure  unit  is  unplugged. 
Electrical shock can cause injury or death.  
 

CAUTIONS:

   

 

Never  expose  eyes  or  skin  to  UVC  light.  
Wear  gloves,  face  shield/glasses  (per  ANSI 
Z87.1) and cover all exposed skin.  

 

Do not touch Emitter

TM 

glass without gloves.  

Damage  to  Emitter  may  result.    Oil  from 
fingerprints  will  permanently  etch  glass  of 
Emitter  and  weaken  structure.    If  necessary, 
clean Emitter using a Steril-Aire cleaning kit, 

isopropyl alcohol and a lint-free wipe may be 
substituted. 

 

UVC  Emitters  are  fragile.    To  prevent 
accidental breakage, handle the UVC Emitter 
with care. 

  

 

Voltages  outside  of  the  range  designed  for 
the  unit  will  void  the  warranty  and  do 
permanent damage to the entire unit. 

  

 

Emitter contains a small quantity of mercury.  
If  an  Emitter  breaks,  clean  and  dispose  with 
the same care as a fluorescent lamp.   

 

UVC  energy  may  cause  damage  to  non-
metallic  components.    Such  components 
shall be protected with UV  resistant material 
such  as  aluminum  foil,  aluminum  duct  tape, 
metallic shields, etc.  

 

The  qualified  installer  or  agency  must  use 
factory  kits  and  accessories  when  installing 
this product. 

 

Once  the  installation  is  complete,  the  UVC  fixture 
should  be  operated  continuously  to  preclude  the 
development  of  mold  and  bacteria.    It  is  not 
recommended to cycle the Emitters by time clock or 
fan operation.   

 
 

ESE 1 SERIES 

ENHANCED SINGLE ENDED 

FIXTURE, 24” – 61” EGTS 

120-277 V 

Part Number 11003000 

 

Patents 6,297,924/ 6,280,686/ 6,313,470/ 6,372,186/ 6,423,882/ 6,500,267/ 6,589,476/ 
6,627,000/ 6,783,578/

 

7,140,749/7,282,728/ 7,459,694 & others pending 

                                                      

Made in the USA 

 

 

Summary of Contents for ESE 1 Series

Page 1: ...er may result Oil from fingerprints will permanently etch glass of Emitter and weaken structure If necessary clean Emitter using a Steril Aire cleaning kit isopropyl alcohol and a lint free wipe may be substituted UVC Emitters are fragile To prevent accidental breakage handle the UVC Emitter with care Voltages outside of the range designed for the unit will void the warranty and do permanent damag...

Page 2: ...stance equal to half the vertical height that the light is covering 6 The Emitter shall also o Be at least 1 away from any heating coil o Not make contact with the air handler blower 7 If applicable replace the outer cover of air handler 8 Remove cover to ESE Fixture 9 Using the fixture base as a template scribe and then create an insertion hole 2 diameter where you want the emitter to be located ...

Page 3: ...components interlock door switches relays motion detectors etc Emitter reaching end of life Replace with new Emitter Reset Power Defective Power supply Replace Power Supply Visibly Weak Emitter Light Bad Wiring Check wiring to emitter Emitter reaching end of life Replace Emitter Emitter too Cold If emitter is at or below 35 F 1 C Emitter is too cold to operate properly Red Orange Emitter Emitter r...

Page 4: ... been investigated by UL 2017 Steril Aire Inc All rights reserved 1391 REPLACEMENT PARTS PART NUMBER EGTS 24 VO Enhanced 24 Single Ended Emitter 21000310 EGTS 30 VO Enhanced 30 Single Ended Emitter 21000410 EGTS 36 VO Enhanced 36 Single Ended Emitter 21000510 EGTS 42 VO Enhanced 42 Single Ended Emitter 21000610 EGTS 50 VO Enhanced 50 Single Ended Emitter 21000910 EGTS 61 VO Enhanced 61 Single Ende...

Reviews: