19
Table 7 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve
*Minimum Load Valve energized.
NOTE: These capacity steps may vary due to different capacity
staging sequences.
30RA UNIT SIZE
CONTROL
STEPS
LOADING SEQ A
LOADING SEQ B
% Displacement
Compressor
% Displacement
Compressor
010 (50/60 Hz)
1
2
69/ 71
100/100
A1*
A1
—
—
—
—
015 (60 Hz)
1
2
79
100
A1*
A1
—
—
—
—
015 (50 Hz)
1
2
3
28
50
100
A1*
A1
A1,A2
—
—
—
—
—
—
018 (50/60 Hz)
1
2
3
32/ 31
50/ 50
100/100
A1*
A1
A1,A2
—
—
—
—
—
—
022 (50/60 Hz)
1
2
3
27/ 35
42/ 50
100/100
A1*
A1
A1,A2
—
—
—
—
—
—
025 (50/60 Hz)
1
2
3
38/ 37
50/ 50
100/100
A1*
A1
A1,A2
—
—
—
—
—
—
030
1
2
3
39
50
100
A1*
A1
A1,A2
—
—
—
—
—
—
032
1
2
3
4
15
25
60
100
A1*
A1
A1,A2
A1,A2,B1
30
40
65
100
B1*
B1
A1,B1
A1,A2,B1
035 (50/60 Hz)
1
2
3
4
16/25
25/33
60/67
100
A1*
A1
A1,A2
A1,A2,B1
32/25
40/33
65/67
100
B1*
B1
A1,B1
A1,A2,B1
040
1
2
3
4
24
32
63
100
A1*
A1
A1,A2
A1,A2,B1
29
37
68
100
B1*
B1
A1,B1
A1,A2,B1
042
1
2
3
4
5
18
25
50
75
100
A1*
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
18
25
50
75
100
B1*
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
045 (60 Hz)
1
2
3
4
5
15
22
44
72
100
A1*
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
15
22
44
72
100
B1*
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
045 (50 Hz), 050
1
2
3
4
5
19
25
50
77
100
A1*
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
19
25
50
77
100
B1*
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
055
1
2
3
4
5
20
25
50
75
100
A1*
A1
A1,B1
A1,A2,B1
A1,A2,B1,B2
20
25
50
75
100
B1*
B1
A1,B1
A1,B1,B2
A1,A2,B1,B2
Summary of Contents for AquaSnap 30RA010
Page 6: ...6 Fig 1 Typical Control Box for 30RA010 030 022 030 Shown ...
Page 7: ...7 Fig 2 Typical Control Box for 30RA032 055 042 055 Shown ...
Page 8: ...8 Fig 3 Wiring Schematic 30RA010 018 30RA010 018 AQUA SNAP ...
Page 10: ...10 Fig 4 Wiring Schematic 30RA022 030 30RA022 030 AQUA SNAP ...
Page 11: ...11 Fig 4 Wiring Schematic 30RA022 030 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 022 030 ...
Page 12: ...12 Fig 5 Wiring Schematic 30RA032 040 30RA032 040 AQUA SNAP ...
Page 13: ...13 Fig 5 Wiring Schematic 30RA032 040 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 032 040 ...
Page 14: ...14 Fig 6 Wiring Schematic 30RA042 055 30RA042 055 AQUA SNAP ...
Page 15: ...15 Fig 6 Wiring Schematic 30RA042 055 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 042 055 ...