57
Table 29 — Alarm and Alert Codes (cont)
LEGEND
ALARM/
ALERT
CODE
ALARM
OR
ALERT
DESCRIPTION
WHY WAS THIS
ALARM
GENERATED?
ACTION TAKEN
BY CONTROL
RESET
METHOD
PROBABLE
CAUSE
T301
Alert
Cooler Pump 2
Scheduled
Maintenance Due
Pump 2 Service
Countdown (P.2.DN)
expired. Complete pump 2
maintenance and
enter 'YES' for Pump 1
Maintenance Done
(P.2.MN) item.
None
Automatic
Routine pump
maintenance
required
T302
Alert
Strainer Blowdown
Scheduled
Maintenance Due
Strainer Service
Countdown (S.T.DN)
expired. Complete strainer
blowdown and enter 'YES' for
Strainer Maintenance Done
(S.T.MN) item.
None
Automatic
Routine strainer
maintenance
required
T303
Alert
Condenser Coil
Maintenance Due
Coil Service Countdown
(C.L.DN) expired.
Complete condenser coil
cleaning and enter 'YES'
for Coil Maintenance Done
(C.L.MN) item.
None
Automatic
Routine condenser
coil maintenance
required
T950
Alert
Loss of Communication
with Water System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
WSM forces removed.
Chiller runs under own
control
Automatic
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
T951
Alert
Loss of Communication
with Flotronic™ System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
FSM forces removed.
Chiller runs under own
control
Automatic
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
T952
Alert
Loss of Communication
with Hydronic System
Manager
No communications have
been received by the MBB
within 5 minutes of last
transmission
HSM forces removed.
Chiller runs under own
control
Automatic
Failed module, wiring
error, failed
transformer, loose
connection plug,
wrong address
S
CN —
Sterlco
Comfort Network
EMM
—
Energy Management Module
EWT
—
Entering Fluid Temperature
FSM
—
Flotronic™ System Manager
HSM
—
Hydronic System Manager
LCW
—
Leaving Chilled Water
LWT
—
Leaving Fluid Temperature
MBB
—
Main Base Board
OAT
—
Outdoor-Air Temperature
SCT
—
Saturated Condensing Temperature
TXV
—
Thermostatic Expansion Valve
WSM —
Water System Manager
Summary of Contents for AquaSnap 30RA010
Page 6: ...6 Fig 1 Typical Control Box for 30RA010 030 022 030 Shown ...
Page 7: ...7 Fig 2 Typical Control Box for 30RA032 055 042 055 Shown ...
Page 8: ...8 Fig 3 Wiring Schematic 30RA010 018 30RA010 018 AQUA SNAP ...
Page 10: ...10 Fig 4 Wiring Schematic 30RA022 030 30RA022 030 AQUA SNAP ...
Page 11: ...11 Fig 4 Wiring Schematic 30RA022 030 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 022 030 ...
Page 12: ...12 Fig 5 Wiring Schematic 30RA032 040 30RA032 040 AQUA SNAP ...
Page 13: ...13 Fig 5 Wiring Schematic 30RA032 040 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 032 040 ...
Page 14: ...14 Fig 6 Wiring Schematic 30RA042 055 30RA042 055 AQUA SNAP ...
Page 15: ...15 Fig 6 Wiring Schematic 30RA042 055 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 042 055 ...