CL-7
III. Unit Start-Up (cont)
PRESS ESCAPE KEY TO DISPLAY ‘RSET’. PRESS DOWN ARROW KEY TO DISPLAY ‘SLCT’.
PRESS ENTER KEY.
RECORD CONFIGURATION INFORMATION BELOW:
SLCT (Setpoint and Ramp Load Configuration)
PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE
ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS.
RECORD CONFIGURATION INFORMATION BELOW:
SETPOINT
SUBMODE
ITEM
DISPLAY
DESCRIPTION
VALUE
SLCT
SETPOINT AND RAMP LOAD
CLSP
X
COOLING SETPOINT SELECT
RL.S
ENBL/DSBL
RAMP LOAD SELECT
CRMP
X.X
COOLING RAMP LOADING
SCHD
XX
SCHEDULE NUMBER
Z.GN
X.X
DEADBAND MULTIPLIER
SUBMODE
ITEM
DISPLAY
DESCRIPTION
VALUE
COOL
COOLING SETPOINTS
CSP.1
XXX.X °F
COOLING SETPOINT 1
CSP.2
XXX.X °F
COOLING SETPOINT 2
CSP.3
XXX.X °F
ICE SETPOINT
HEAD
HEAD PRESSURE SETPOINTS
HD.P.A
XXX.X °F
CALCULATED HP SETPOINT A
HD.P.B
XXX.X °F
CALCULATED HP SETPOINT B
FRZ
BRINE FREEZE SETPOINT
BR.FZ
XXX.X °F
BRINE FREEZE POINT
Summary of Contents for AquaSnap 30RA010
Page 6: ...6 Fig 1 Typical Control Box for 30RA010 030 022 030 Shown ...
Page 7: ...7 Fig 2 Typical Control Box for 30RA032 055 042 055 Shown ...
Page 8: ...8 Fig 3 Wiring Schematic 30RA010 018 30RA010 018 AQUA SNAP ...
Page 10: ...10 Fig 4 Wiring Schematic 30RA022 030 30RA022 030 AQUA SNAP ...
Page 11: ...11 Fig 4 Wiring Schematic 30RA022 030 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 022 030 ...
Page 12: ...12 Fig 5 Wiring Schematic 30RA032 040 30RA032 040 AQUA SNAP ...
Page 13: ...13 Fig 5 Wiring Schematic 30RA032 040 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 032 040 ...
Page 14: ...14 Fig 6 Wiring Schematic 30RA042 055 30RA042 055 AQUA SNAP ...
Page 15: ...15 Fig 6 Wiring Schematic 30RA042 055 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 042 055 ...