Installation, Operation and Maintenance Manual – FMA 3000
Ref: 3000/T/6/VH
19
8. – INSTALLATION INSTRUCTIONS
Take any necessary precautions to prevent bumping the filter. Lift the device by using the
anchoring points at the top.
Make sure the installation point has the minimum operating pressure.
o
The discharge pipe should be dimensioned to generate a minimum pressure loss
at a flow rate of 30 m³/h.
o
In facilities with a working pressure above 6 bar, we recommend installing a ball
valve on the discharge pipe in order to adjust the washing flow.
NOTE
MINIMUM OPERATING PRESSURE IS 2 BAR BETWEEN FILTER OUTPUT
AND DRAIN VALVE.
IN THE EVENT THAT THE DRAINAGE IS REDIRECTED, THERE MAY BE
BACKPRESSURE DUE TO PRESSURE DROP AND INCREASES IN
HEIGHT.
Install filter vertically, make sure to leave enough space to allow easy access to your
device for future treatments and to perform maintenance safely. See section 6.
Orient the filter in the pipe according to the arrows indicating water flow direction.
It is recommended to install shutoff valves at the inlet and outlet of the filter to allow
insulation from the pipe. To avoid outages during maintenance, it is recommended to
install a bypass.
We recommend installing an anti-backflow valve at the outlet to prevent water hammer in
the filter.
The electrical wiring can only be carried out by a licensed electrician in accordance with
section 12.1
When installing the filter, prevent water from splashing onto the electrical components or
the control panel.
Summary of Contents for FMA-3000
Page 5: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 5 ...
Page 7: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 7 2 WARRANTY ...
Page 17: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 17 ...
Page 38: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 38 ...
Page 39: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 39 ...