Installation, Operation and Maintenance Manual – FMA 3000
Ref: 3000/T/6/VH
30
ADJUSTING THE SETPOINT OF THE DIFFERENTIAL PRESSURE SENSOR
The differential pressure sensor is regulated by the S3 selector block as shown in the following
table. While the differential pressure is maintained below the setpoint, no cycle start signal is
generated, but when the differential pressure is greater, it works as a closed contact in the
differential pressure sensor and a cleaning cycle will be initiated if this condition is maintained for
at least 5 seconds.
Setpoint
Position
S3
1 – ON
0 – OFF
1 2 3 4
Atm.
psi
00
0 0 0 0
The sensor has not been activated
01
1 0 0 0
0.1
2
02
0 1 0 0
0.3
4
03
1 1 0 0
0.4
6
04
0 0 1 0
0.5
8
05
1 0 1 0
0.7
10
06
0 1 1 0
0.8
12
07
1 1 1 0
1.0
14
08
0 0 0 1
1.1
16
09
1 0 0 1
1.2
18
10
0 1 0 1
1.4
20
11
1 1 0 1
1.5
22
12
0 0 1 1
1.6
24
13
1 0 1 1
1.8
26
14
0 1 1 1
1.9
28
15
1 1 1 1
2.0
30
WARNING!
CHANGING THIS VALUE IS NOT RECOMMENDED.
NEVER INCREASE THE DIFFERENTIAL, ONLY CHANGE IT TO SMALLER
VALUES TO FORCE EARLIER DEVICE SELF-CLEANING.
Summary of Contents for FMA-3000
Page 5: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 5 ...
Page 7: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 7 2 WARRANTY ...
Page 17: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 17 ...
Page 38: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 38 ...
Page 39: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 39 ...