13. – NOTICES AND ALARMS
1 beep every 15 seconds – Normal operation.
2 beeps every 15 seconds – Continuous cleaning problem alarm.
3 beeps every 15 seconds – Low battery.
6 beeps after ON or after RESET – It indicates that the programming unit is in
calibration mode. It should not normally occur but if it is the case, then the JP1 jumper
has been placed in calibration mode (free right pin), the process should be completed as
follows: to ensure that the differential pressure indicated by the sensor is zero
(disconnect the red and black pipes from the sensor if necessary), and press the RESET
button. Change the position of JP1 jumper to normal with the left pin of the jumper free
and press the RESET button again.
When the program indicates a continuous cleaning problem through 2 beeps every 15 seconds, it
means there is a continuous differential signal in the differential pressure switch. In the event that
this occurs, the system starts cleaning at time intervals to be defined in S1 selector for intervals
between cleaning operations. The cause of the problem should be detected and removed and,
once the problem has been fixed, press the RESET button to send a signal to the programming
unit that the problem has been solved.
Summary of Contents for FMA-3000
Page 5: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 5 ...
Page 7: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 7 2 WARRANTY ...
Page 17: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 17 ...
Page 38: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 38 ...
Page 39: ...Installation Operation and Maintenance Manual FMA 3000 Ref 3000 T 6 VH 39 ...