9.4 Pneumatic connections
Warning
Check that the values of pneumatic supply available are compatible with those
reported on the label of the FTC smart positioner. User must consider and take all
precautions to avoid that pressurized parts are not used out of specified range
and to avoid exposure to fire.
Important
For easier maintenance, it is recommended to install a filter with five micron
cartridge and shut-off valve on the supply connection.
It is recommended to follow these steps:
-
the pressure line pipe has to be sized to avoid significant pressure drop during the actuator stroke;
-
the piping between FTC smart positioner and actuator has to be ¼” and shorter as possible;
-
during piping connection be careful to keep clean the internal side of piping and fittings, free from
threaded sealing material or any other contaminants;
-
the FTC smart positioner is suitable for single acting actuators and double acting actuators (with or
without spring):
o
for double acting actuators (without spring):
i. Port IN must be connected to the supply line;
ii. Port OUT2 (or M6 thread hole) must be connected to the actuator chamber that has to
vent at signal fail position (no power);
iii. Port OUT1 must be connected to the actuator chamber that has to be pressurized at
signal fail position (no power);
o
for double acting actuators (with spring):
i. Port IN must be connected to the supply line;
ii. Port OUT2 (or M6 thread hole) must be connected to the actuator chamber that has to
vent at signal fail position (no power);
iii. Port OUT1 must be connected to the actuator chamber that has to be pressurized at
signal fail position (no power);
o
for single acting actuators:
i. Port IN must be connected to the supply line;
ii. Port OUT2 (or M6 thread hole) must be connected to the actuator chamber that has to
vent at signal fail position (no power);
iii. Port OUT1 must be plugged with tight plug suitable for the pressure rating and area
classification;
-
no load or bending moment are allowed on pneumatic connection;
-
the supply pressure must be lower than actuator design pressure;
-
to check the correct mounting of the pneumatic connections, pressurize the FTC smart positioner
without any power signal and check if the actuator moves to the 0% signal position.