11
Spacing multi-row collector fields
If high snow loads are to be expected, the fastening hooks
have to be mounted above the rafters (that means that
the support must lie on the rafter;alternatively, a higher
number of fastening hooks can be considered, depending
on the load). If the loading capacity in the battens is not
given, an assembly on the rafter is recommended.
1410002 Rooftile bracket V2 without lead
1410003 Rooftile bracket V2 with lead
1410004 Roof bracket plain tile without lead
1410005 Roof bracket plain tile with lead
Distance measures fastening hooks
Fastening hooks in
roof covering
Initial position:
top edge
roof tiles
Horizontal
measure
FKF 200 H FKF 200 V FKF 240 H FKF 240 V FKF 270 H FKF 270 V
Measure A
171,3 cm
122 cm
212 cm
122 cm
239.3 cm
122 cm
Vertical
measure
Tolerance
FKF 200 H
+ / - 10 cm
FKF 200 V
+ / - 10 cm
FKF 240 H
+ / - 10 cm
FKF 240 V
+ / - 10 cm
FKF 270 H
+ / - 10 cm
FKF 270 V
+ / - 10cm
Measure H1
97 cm 151 cm
97 cm
187 cm
97 cm 214 cm
Measure H2
137 cm 191 cm
137 cm
227 cm
137 cm 254 cm
Measure H3
214 cm 322 cm
214 cm
394 cm
214 cm 448 cm
Measure H4
254 cm 362 cm
254 cm
434 cm
254 cm 488 cm
Measure H5
331 cm 493 cm
331 cm
601 cm
331 cm 682 cm
x
117 cm 171 cm
117 cm
207 cm
117 cm 234 cm
The next series is given by:
Hn = Hn - 2 + x
whereby n is the number of the row of roof-tiles to
be calculated.
Example FKF 240 H
H6 = H6 - 2 + x
H6 = H4 + x (Height H4 see table)
H6 = 254 cm + 117 cm
H6 = 371 cm
For each collector row two fastening hooks
are needed.
The vertical measures H1 to Hn are each
taken on the top edge of the fastening
hooks.
The measures for the installation of the
rooftile brackets are obligatory. Otherwise,
the hydraulic collector connection may
be lying at the height of the mounting
profile which makes it difficult to fasten the
collectors on the profile.
Initial position
Example: Arrangement for 3 rows with 3 collectors each