UL INSTALLATION REQUIREMENTS
STI DOME SERIES
•The enclosure is rated to protect signaling appliances indoors and in areas of indirect weather
exposure. Thecover may be used outdoors only with devices also suitable for outdoor use.
•When covering fire-signaling appliances with this enclosure, some light and sound loss occurs.
Please followthe guidelines listed during installation.
•Strobe light loss values for respective manufacturers are shown below. To determine the new
composite candela valuefor use with this guard refer to the sample calculation shown below for a
manufacturer’s strobe.
•Example: Record the manufacturer's candela value as "A" and the light loss value as "B" and the
assembly valueas "C". For example “Sample Company” has a 60 candela strobe with a 30% light
transmission loss value. Value"A" is now 60. Value "B" is (60 times 30% or 0.30) in this case 18. Now
value "C" equals value "A" minus value"B" or 60-18 = 42 candela light source. Now refer to NFPA
tables for proper room size that the newly establishedvalue "C" will work in. Submittal installation
drawings must show the composite candela value as 42.
•On a dual value strobe such as 15/75 a calculation must be done for each value and the drawing
notationcomposite value for each number on the strobe.
•Ce boîtier est homologué pour protéger les appareils de signalisation d’incendie à l’intérieur et dans les
zones d’expositionindirecte aux intempéries. Le couvercle ne peut être utilisé à l’extérieur qu’avec les
appareils appropriés pour une utilisation àl’extérieur aussi.
•Le fait de couvrir les appareils de signalisation d’incendie au moyen de ce boîtier risque d’entraîner une
certaine perte lumineuseet sonore. Veuillez vous conformer à ces directives lors de l’installation.
•Les valeurs de perte de lumière stroboscopique publiées par les fabricants respectifs sont présentées
ci-dessous. Pourdéterminer la nouvelle valeur candéla composite pour une utilisation avec cette protection, r
eportez-vous au modèle de calculmontré pour le stroboscope d’un fabricant donné.
•Exemple: Inscrivez la valeur candéla « A » du fabricant et la valeur de perte de lumière « B » et la valeur
de l’ensemble « C ».Par exemple, la « Société modèle » possède un stroboscope de 60 candélas avec une
valeur de perte de diffusion lumineusede 30 %. La valeur « A » sera alors de 60. Et la valeur « B » sera dans
ce cas de 18 (60 fois 30 % ou 0,30). À présent, la valeur« C » est égale à la valeur « A » moins la valeur « B »,
ou 60 - 18 = 42 candélas. Reportez-vous maintenant aux tableaux de laNFPA pour la taille correcte de la
pièce compatible avec la valeur « C » nouvellement créée. "C" travailler. Les schémasd’installation à
soumettre doivent afficher la valeur de candéla composite comme étant 42.
•Dans le cas d’un stroboscope double-valeur, telle que 15/75, un calcul doit être effectué pour chaque valeur
et pour la valeurcomposite du schéma des cotes relatif à chaque valeur sur le stroboscope.
CAUTION:
Performance Review - LIGHT DERATING FACTOR
+ Indicates notification appliance can also be used with STI Heater Domes models STI-1229HTR or STI-1229HTR240
SOUND DERATING FACTOR for STI-1215, STI-1217, STI-1219
HORNS: Amseco Audible Horn Sounders: 6.2 dBA; System Sensor: 3.1 dBA
SPEAKERS: Siemens Adapter Series (0.5, 1, or 2 watt taps only): 4.1 dBA
USA Headquarters • 2306 Airport Road • Waterfood • Michigan • 48327-1209 • Phone: 248-673-9898 • Fax: 248-673-1246 • www.sti-usa.com
European Office • Taylor House • 34 Sherwood Road • Bromsgrove • Worcestershire • B60 3DR • Phone: +44 (0)1527 520 999 • www.sti-emea.com
M
anufa
c
tur
e
r
Se
r
ies
STI-1215/
1217/1219
STI-1225/
1227/1229
M
anufa
c
tur
e
r
Se
r
ies
STI-1215/
1217/1219
STI-1225/
1227/1229
ADT SECURITY
ADTG1-V Se
r
ies
20%
32%
HONEYWELL
XLS202 Se
r
ies
33%
34%+
AMSECO
SL24W-153075
22%
37%+
HONEYWELL
XLSG1-HV Se
r
ies
20%
32%+
AMSECO – COLORED LENSES
SL24W-15307 A,B,G
or
R
22%
37%+
HONEYWELL
XLSG1-HOV Se
r
ies
20%
37%+
AMSECO – COLORED LENSES
SL24C-15307 A,B,G
or
R
22%
37%+
MIRCOM
FS-240
22%
37%+
AMSECO – COLORED LENSES
CSL24W-A, B,G
or
R
22%
37%+
MIRCOM
MS Se
r
ies
33%
34%+
AMSECO – COLORED LENSES
CSL24C-A, B,G
or
R
22%
37%+
MIRCOM
MG1-V Se
r
ies
20%
32%+
DETECTION SYSTEMS
GES24 Se
r
ies
27%
37%+
MIRCOM
MG1-HV Se
r
ies
20%
32%+
DETECTION SYSTEMS
GES24-15/75
27%
37%+
MIRCOM
MG1-HOV Se
r
ies
20%
32%+
EST/EDWARDS
2440S Se
r
ies
33%
34%+
MIRTONE
MG1-V Se
r
ies
20%
32%+
EST/EDWARDS
202 Se
r
ies
33%
34%+
NATIONAL TIME&SIGNAL
GES24 Se
r
ies
27%
37%+
EST/EDWARDS
G1-V Se
r
ies
20%
32%+
NATIONAL TIME&SIGNAL
GES24-15/75
27%
37%+
EST/EDWARDS
G1-HV Se
r
ies
20%
32%+
POTTER ELECTRIC
AS-24-153075R
22%
37%+
EST/EDWARDS
G1-HOV Se
r
ies
20%
32%+
POTTER ELECTRIC
AS-24-153075W
22%
37%+
EST/EDWARDS
EG1-V Se
r
ies
20%
32%+
SECUTRON
GES24 Se
r
ies
27%
37%+
EST/EDWARDS
EG1-HV Se
r
ies
20%
32%+
SECUTRON
GES24-15/75
27%
37%+
EST/EDWARDS
EG1-HOV Se
r
ies
20%
32%+
SIEMENS
202 Se
r
ies
33%
34%+
FARADAY LLC
2700
23%
33%+
SIEMENS
G1-V Se
r
ies
20%
32%+
GETEX
GES24 Se
r
ies
27%
37%+
SIEMENS
U-MCS Se
r
ies
23%
33%+
GENTEX
GES24-15/75
27%
37%+
SYSTEM SENSOR
SS24110ADA
26%
36%+
HARRINGTON SIGNAL
GES24 Se
r
ies
27%
37%+
SYSTEM SENSOR
P2,PC2,P4,PC4,SX,SC
39%
28%
HARRINGTON SIGNAL
GES24-15/75
27%
37%+
WHEELOCK
RSS-24MCW
34%
31%
HONEYWELL
XLSG1-V Se
r
ies
20%
32%+
WHEELOCK
RSS-24MCC
36%
35%
ZITON PTY LTD
ZG1-V Se
r
ies
20%
32%+