INSTALLATION INSTRUCTIONS 

SOL 27 PREMIUM S & W COLLECTORS - 230016 & 230017

The air-side inlet pressure should be ser to 5-7 psi less 
than the system start-up (cold) pressure; check it when 
the system has not been fi lled or when the wet side of the 
expansion tank is open to the atmosphere.

!

 

WARNING: SET TING T HE MAXIMUM TANK 
T EM P E R AT U R E   H I G H E R  T H A N   1 4 0

F AT 

THE CONTROL UNIT IS PERMISSABLE ONLY WITH A 
THERMOSTATICALLY-CONROLLED DHW MIXING VALVE. 
OTHERWISE THERE CAN BE A RISK OF SCALDING AT THE 
DRAWOFF POINT.

!

 

IMPORTANT: ALL SENSOR WIRING SHOULD BE 
RATED FOR EXPECTED TEMPERATURES AND MUST 

BE PROTECTED FROM DEGRADATION AND ELECTRICAL 
INTERFERENCE. FOR MORE INFORMATION, CONSULT THE 
USER MANUAL FOR THE CONTROLLER.

Solar Loop

Use only a mixture of 50% food-grade Propylene Glycol and 
de-ionized water in the solar loop.

!

 

WARNING: FLUID MAY BE DISCHARGED AT HIGH 
TEMPERATURE AND/OR PRESSURE.

NO OTHER FLUID SHALL BE USED THAT WOULD CHANGE 
THE ORIGINAL CLASSIFICATION OF THE SYSTEM. UNAU-
THORIZED ALTERATIONS TO THIS SYSTEM COULD RESULT 
IN A HAZARDOUS CONDITION, AND COULD VOID THE 
MANUFACTURER'S WARRANTY.

Shut-down

Except for repair and/or emergency, the control unit and 
the pump must remail powered and activated in order to 
avoid overheating the collectors. Prior to shutting down 
the system for repairs, cover the solar collectors or work at 
night.

If emergency shut-down is needed, unplug the control unit 
and call for service.

2 Collector 

Basics

The SOL 27 Premium is a highly effi cient solar thermal 
collector. The net absorber surface of over 25 ft² helps result 
in a maximum output og 31,300 BTU/day per panel (SRCC 
clear day rating). The SOL 27 Premium also offers features 
such as a highly selective absorber coating, low-iron, 
tempered solar glazing, and very effective insulation around 
the absorber plate. The internal fl uid tubes are copper and 
the absorber plate is aluminum.

The internal fl uid tubes are organized in a "harp style" 
confi guration. This consists of two headers. The top header 
is split in the middle, resulting in half of the tubes directing 
fl ow downward, and half directing fl ow upward.

The collector converts sunlight into heat. Light penetrates 
the glass cover, which is pre-stressed, highly transparent 

Summary of Contents for 230016

Page 1: ...OPERATION AND INSTALLATION HIGH PERFORMANCE FLAT PLATE COLLECTOR SOL 27 PREMIUM S SOL 27 PREMIUM W CLICK ANYWHERE on THIS PAGE to RETURN to SOLAR HOT WATER GUIDES at InspectApedia com...

Page 2: ...instructions or improper use voids the warranty Save these instructions for future reference Installers should leave these instructions with the consumer If you have any questions regarding the insta...

Page 3: ...E ORIGINAL CLASSIFICATION OF THE SYSTEM UNAU THORIZED ALTERATIONS TO THIS SYSTEM COULD RESULT IN A HAZARDOUS CONDITION AND COULD VOID THE MANUFACTURER S WARRANTY Shut down Except for repair and or eme...

Page 4: ...ght 85 5 2171 mm 46 1 1171 mm Width 46 1 1171 mm 85 5 2171 mm Depth 3 8 96 mm 3 8 96 mm Weight 88 2 lb 40 kg 89 3 lb 40 5 kg Casing material Aluminum corrosion resistant Glass cover ESG Glass thicknes...

Page 5: ...llation Pipework Installation Use copper or stainless steel pipes or corrugated stainless steel hoses for the supply and return lines Pipe diameter is depended on length of run and expected ow rates R...

Page 6: ...e nighttime winter temperatures below 30 F may need thicker pipe insulation to prevent pipe freeze ups or slushing of the antifreeze mixture Minimum Insulation Thickness Diameter of Pipe Minimum thick...

Page 7: ...re it is seated in the groove of the collector trim at the top and in the bottom groove of the collector 5 When the grip is positioned correctly tighten the xing screws 6 Attach the remaining grips on...

Page 8: ...TO ONE ANOTHER IF THE SPACER IS REMOVED BEFOREHAND THE CONNECTOR MAY BE DAMAGED WHEN THE SECOND COLLECTOR IS PUSHED INTO PLACE Inter panel connector Spacer Connecting clip 1 Insert the plug in connec...

Page 9: ...en collector and plug in connection 3 Secure the connecting clip by pushing down on the locking tab 4 Install the inlet of the collector array in the same manner Collector Sensor The correct connectio...

Page 10: ...ews in accordance with DIN 571 at least 10 x 80 of stainless steel per collector If multiple arrays of collectors are being installed on a at roof one behind another the recommended spacing between th...

Page 11: ...arrays either SOL 27 Premium S or W panels can be used Use the following pictures and tables for reference when determining how to install your tilt mount collectors Flush Mount Vertical Side by side...

Page 12: ...k 30 60 560203 0 1 1 1 Horizontal X Brace 560206 0 0 1 2 Double Mounting Frame 230170 1 2 3 4 Frame Connector Kit SFC 001 0 1 2 3 Mounting L Bracket Flashing Kits Asphalt 560104 L 4 8 12 16 S5U L 102...

Page 13: ...e and isolation valve Flow Meter S Temperature Sensor T Thermometer Expansion Tank Air Fill Valve Disconnect Valve Solar Collectors S2 S3 T S4 Solar Storage Tank Coil in tank Heat Exchanger mixing val...

Page 14: ...ts that are coated with soapy water and watching the pressure gauge over time Bear in mind that the pressure gauge will vary some based on temperature of the air so one must try to read the pressure a...

Page 15: ...e collector framewall or absorber plate 5 To glass breakage 6 To conditions resulting from the introduction of harmful chemicals caustic uids or liquids deleterious to copper tubing including improper...

Page 16: ...WKH 65 7KLV DZDUG RI FHUWLILFDWLRQ LV VXEMHFW WR DOO WHUPV DQG FRQGLWLRQV RI WKH 3URJUDP JUHHPHQW DQG WKH GRFXPHQWV LQFRUSRUDWHG WKHUHLQ E UHIHUHQFH 7KLV GRFXPHQW PXVW EH UHSURGXFHG LQ LWV HQWLUHW 2 7...

Page 17: ...KH 65 7KLV DZDUG RI FHUWLILFDWLRQ LV VXEMHFW WR DOO WHUPV DQG FRQGLWLRQV RI WKH 3URJUDP JUHHPHQW DQG WKH GRFXPHQWV LQFRUSRUDWHG WKHUHLQ E UHIHUHQFH 7KLV GRFXPHQW PXVW EH UHSURGXFHG LQ LWV HQWLUHW 2 72...

Page 18: ...site Site System operator Installation site Collectors Collectors number type Collector surface area System speci cations System height Pipe run length Ventilation Solar uid type concentration Max ow...

Reviews: