INSTALLATION INSTRUCTIONS 

SOL 27 PREMIUM S & W COLLECTORS - 230016 & 230017

6.  Inulate the connection using the provided thermal 
insulation.

Inlet & Outlet Connection

The inlets & outlets are plug-in style connections identical to 
the inter-panel connections. The installation method is the 
same as the inter-panel connection.

Connector clip

Outlet connector

Inlet connector

1.  Insert the inlet/outlet connector into the collector 
connection on each end of the array. Make sure to insert the 
connection with a sensor well on the end of the array that 
you intend to be the hot side (the outlet of fl ow of the array).

2.  Fit the connecting clip at the junction between collector 

and plug-in connection.

3.  Secure the connecting clip by pushing down on the 
locking tab.

4.  Install the inlet of the collector array in the same 
manner.

Collector Sensor

The correct connection of the collector sensor is crucial to 
the correct function of the solar system.

1.   Secure the sensor lead.

2.  Connect the sensor lead to the controller. Be sure 
to properly insulate the sensor wire using standard 
procedures.

Lightning Protection

If the building has a lightning protection system, the 
collector casing, mounting frame and pipework must be 
connected to the existing lightning protection scheme.

Connect the collector to the lightning protection system 
using screw fi ttings. Use two stainless steel seft-tapping 
screws per collector.

1.  Pre-drill the holes. Position the drill holes on the lower 
part of the front of the collector in the area shaded in the 
following illustration. When drilling the holes, maintain a 
distance of at least 4 inches from the corner of the collector 
casing.

Summary of Contents for 230016

Page 1: ...OPERATION AND INSTALLATION HIGH PERFORMANCE FLAT PLATE COLLECTOR SOL 27 PREMIUM S SOL 27 PREMIUM W CLICK ANYWHERE on THIS PAGE to RETURN to SOLAR HOT WATER GUIDES at InspectApedia com...

Page 2: ...instructions or improper use voids the warranty Save these instructions for future reference Installers should leave these instructions with the consumer If you have any questions regarding the insta...

Page 3: ...E ORIGINAL CLASSIFICATION OF THE SYSTEM UNAU THORIZED ALTERATIONS TO THIS SYSTEM COULD RESULT IN A HAZARDOUS CONDITION AND COULD VOID THE MANUFACTURER S WARRANTY Shut down Except for repair and or eme...

Page 4: ...ght 85 5 2171 mm 46 1 1171 mm Width 46 1 1171 mm 85 5 2171 mm Depth 3 8 96 mm 3 8 96 mm Weight 88 2 lb 40 kg 89 3 lb 40 5 kg Casing material Aluminum corrosion resistant Glass cover ESG Glass thicknes...

Page 5: ...llation Pipework Installation Use copper or stainless steel pipes or corrugated stainless steel hoses for the supply and return lines Pipe diameter is depended on length of run and expected ow rates R...

Page 6: ...e nighttime winter temperatures below 30 F may need thicker pipe insulation to prevent pipe freeze ups or slushing of the antifreeze mixture Minimum Insulation Thickness Diameter of Pipe Minimum thick...

Page 7: ...re it is seated in the groove of the collector trim at the top and in the bottom groove of the collector 5 When the grip is positioned correctly tighten the xing screws 6 Attach the remaining grips on...

Page 8: ...TO ONE ANOTHER IF THE SPACER IS REMOVED BEFOREHAND THE CONNECTOR MAY BE DAMAGED WHEN THE SECOND COLLECTOR IS PUSHED INTO PLACE Inter panel connector Spacer Connecting clip 1 Insert the plug in connec...

Page 9: ...en collector and plug in connection 3 Secure the connecting clip by pushing down on the locking tab 4 Install the inlet of the collector array in the same manner Collector Sensor The correct connectio...

Page 10: ...ews in accordance with DIN 571 at least 10 x 80 of stainless steel per collector If multiple arrays of collectors are being installed on a at roof one behind another the recommended spacing between th...

Page 11: ...arrays either SOL 27 Premium S or W panels can be used Use the following pictures and tables for reference when determining how to install your tilt mount collectors Flush Mount Vertical Side by side...

Page 12: ...k 30 60 560203 0 1 1 1 Horizontal X Brace 560206 0 0 1 2 Double Mounting Frame 230170 1 2 3 4 Frame Connector Kit SFC 001 0 1 2 3 Mounting L Bracket Flashing Kits Asphalt 560104 L 4 8 12 16 S5U L 102...

Page 13: ...e and isolation valve Flow Meter S Temperature Sensor T Thermometer Expansion Tank Air Fill Valve Disconnect Valve Solar Collectors S2 S3 T S4 Solar Storage Tank Coil in tank Heat Exchanger mixing val...

Page 14: ...ts that are coated with soapy water and watching the pressure gauge over time Bear in mind that the pressure gauge will vary some based on temperature of the air so one must try to read the pressure a...

Page 15: ...e collector framewall or absorber plate 5 To glass breakage 6 To conditions resulting from the introduction of harmful chemicals caustic uids or liquids deleterious to copper tubing including improper...

Page 16: ...WKH 65 7KLV DZDUG RI FHUWLILFDWLRQ LV VXEMHFW WR DOO WHUPV DQG FRQGLWLRQV RI WKH 3URJUDP JUHHPHQW DQG WKH GRFXPHQWV LQFRUSRUDWHG WKHUHLQ E UHIHUHQFH 7KLV GRFXPHQW PXVW EH UHSURGXFHG LQ LWV HQWLUHW 2 7...

Page 17: ...KH 65 7KLV DZDUG RI FHUWLILFDWLRQ LV VXEMHFW WR DOO WHUPV DQG FRQGLWLRQV RI WKH 3URJUDP JUHHPHQW DQG WKH GRFXPHQWV LQFRUSRUDWHG WKHUHLQ E UHIHUHQFH 7KLV GRFXPHQW PXVW EH UHSURGXFHG LQ LWV HQWLUHW 2 72...

Page 18: ...site Site System operator Installation site Collectors Collectors number type Collector surface area System speci cations System height Pipe run length Ventilation Solar uid type concentration Max ow...

Reviews: