iNSTallaTiON
Commissioning
www.stiebel-eltron.com
HSBB 200 S (GB) |
15
12.3 Remote control
12.3.1 FE 7 remote control
3
1
1
2
3
26
2
1
01
000
8
With the FE 7 remote control you can adjust the set room temper-
ature for the heating circuit by ± 5 °C in automatic mode only. You
can also select the operating mode.
f
f
Connect the remote control to AA01-X1.13.
12.3.2 FET remote control
1
2
3
4
5
6
H
L
+
D
00000
82
61
2
With the FET remote control you can adjust the set room temper-
ature for the heating circuit by ± 5 °C and change the operating
mode.
f
f
Connect the remote control to AA01-X1.2.
13. Commissioning
Our customer support can assist with commissioning, which is a
chargeable service.
If the appliance is intended for commercial use, observe the rules
of the relevant Health & Safety at Work Act during commissioning.
For further details, check with your local authorising body.
13.1 Checks before commissioning the heat pump
manager
!
Material losses
Observe the maximum system temperature in underfloor
heating systems.
f
f
Check that the heating system is filled to the correct pressure
and the quick-action air vent valve is closed.
f
f
Check whether the outside temperature sensor is correctly
placed and connected.
f
f
Check whether the power supply is connected correctly.
f
f
Check whether the signal cable to the heat pump (bus cable)
is correctly connected.
High limit safety cut-out
Note
At temperatures below –15 °C the high limit safety cut-out
may respond. The appliance may be subjected to these
temperatures during storage or transport.
f
f
Check whether the high limit safety cut-out has tripped.
1
D
00000
70
88
5
1 High limit safety cut-out reset button