background image

iNSTallaTiON 

 

installation

www.stiebel-eltron.com 

HSBB 200 S (GB) | 

9

!

 

Material losses

Never switch on the power before filling the system.

 

Note 

With a conductivity >1000 μS/cm, desalination treatment 

is recommended in order to avoid corrosion.

 

Note 

If you treat the fill water with inhibitors or additives, the 

same limits as for desalination apply.

 

Note 

Suitable appliances for water softening, as well as for 

filling and flushing heating systems, can be obtained via 

trade suppliers.

11.5.1  Flushing out the hot water system

Before turning on the water supply, open all taps. Allow the sys-

tem to fill and flush out all flux and debris from the installation.

11.5.2  Filling the heating system

Check whether volume and pre-charge pressure of the diaphragm 

expansion vessel match the requirements of the heating system 

(see chapter "Specification / Data table").

D

00000

70

88

6

f

f

Remove the protective cap of the fill valve on the diaphragm 

expansion vessel.

f

f

Check the pre-charge pressure of the diaphragm expansion 

vessel using a pressure gauge. Please note that the system 

must be non-pressurised.

f

f

Refit the protective cap to the fill valve.

In the delivered condition, the 3-way diverter valve of the mul-

tifunction assembly is in its centre position, so that the heating 

circuit and the heat exchanger for DHW heating are filled evenly. 

When power is switched on, the 3-way diverter valve automatically 

switches to heating mode.
To fill or drain the system later, you must first place the 3-way 

diverter valve into its centre position.

To set the heat pump manager:

f

f

With the MENU key, call up the main menu.

f

f

Select the menu or value and confirm with OK:

„



DIAGNOSIS



…

RELAY TEST SYSTEM

…

…

DRAIN HYD

D

00000

70

88

3

f

f

Fill the heating system via the drain valve.

D

00000

70

88

8

f

f

After filling the heating system, check the cap valve for 

tightness.

f

f

Vent the pipework.

11.5.3  DHW cylinder filling

!

 

Material losses

Some fluxes used to solder pipes and fittings need to be 

flushed out with hot water.

f

f

Heat the cylinder to its normal operating tempera-

ture and flush all pipe work with hot water to ensure 

all flux and debris is removed from the system.

f

f

Fill the DHW cylinder via the the drain valve in compliance 

with the UK Water Supply (Water Fittings) Regulations 1999, 

Section 8 G24.

f

f

Open all downstream draw-off valves/taps until the appli-

ance is full and the pipework is free of air.

f

f

Adjust the flow rate. For this, observe the maximum permis-

sible flow rate with a fully opened tap (see chapter "Specifi-

cation / Data table"). If necessary reduce the flow rate at the 

butterfly valve of the safety assembly.

f

f

Carry out a tightness check.

f

f

Check the safety valve.

Summary of Contents for 236916

Page 1: ...OPERATION AND INSTALLATION Cylinder and hydraulic module HSBB 200 S GB...

Page 2: ...ring diagram 20 16 4 Details on energy consumption 22 16 5 Data table 22 GUARANTEE ENVIRONMENT AND RECYCLING SPECIAL INFORMATION The appliance may be used by children aged 8 and older and persons with...

Page 3: ...nt the risk are listed 1 2 2 Symbols type of risk Symbol Type of risk Injury Electrocution Burns burns scalding 1 2 3 Keywords KEYWORD Meaning DANGER Failure to observe this information will result in...

Page 4: ...nce description The appliance comprises a hydraulic module and an integral DHW cylinder and is equipped with a removable front casing The appli ance is connected hydraulically and electrically to the...

Page 5: ...If you cannot remedy the fault notify your qualified contractor To facilitate and speed up your request provide the number from the type plate 000000 0000 000000 No 000000 0000 000000 Made in Germany...

Page 6: ...osses Store and transport the appliance at temperatures be tween 20 C to 60 C Handling If possible transport the appliance to the installation site on the non returnable pallet Alternatively transport...

Page 7: ...ements or steel pipes Material losses The products of corrosion e g rusty sludge can settle in the heating system components and can result in a lower output or fault shutdowns due to reduced cross se...

Page 8: ...ine Stainless steel copper and plastic are approved materials 11 4 2 Installing the DHW circulation line if applicable A DHW circulation line with external DHW circulation pump can be fitted to the DH...

Page 9: ...re position so that the heating circuit and the heat exchanger for DHW heating are filled evenly When power is switched on the 3 way diverter valve automatically switches to heating mode To fill or dr...

Page 10: ...dance with relevant regulations Before any work on the appliance disconnect all poles from the power supply WARNING Electrocution Only use a permanent connection to the power supply Ensure the applian...

Page 11: ...rol voltage Appliance function Effect of the electric emergency booster heater Mono energetic operation If the heat pump undershoots the dual mode point the electric emergency booster heater safeguard...

Page 12: ...xtra low voltage X1 1 CAN A L H L H CAN connection for heat pump and WPE heat pump extension X1 2 CAN B L H L H CAN connection for FET remote control and ISG Internet Service Gateway X1 3 Signal Earth...

Page 13: ...PE 2nd heat source heating X2 13 L N PE L N PE Cooling X2 14 Mixer OPEN N PE Mixer CLOSE 5 N PE 6 Mixer heating circuit 2 X2 14 1 Mixer OPEN X2 14 2 Mixer CLOSE X2 15 Mixer OPEN N PE Mixer CLOSE 5 N P...

Page 14: ...doors or air ducts Observe the following minimum clearances 2 5 m above the ground and 1 m to the side of windows and doors Installation f f Remove the cover f f Secure the base with the screw suppli...

Page 15: ...e observe the rules of the relevant Health Safety at Work Act during commissioning For further details check with your local authorising body 13 1 Checks before commissioning the heat pump manager Mat...

Page 16: ...Condensation caused by the temperature falling below the dew point can lead to material losses HSBB is there fore exclusively approved for area cooling Adjusting the heat pump manager settings for ar...

Page 17: ...fication Dimensions and connections Checking replacing the protective anode f f Check the protective anode after the first two years of use and replace if necessary Check that the maximum transition r...

Page 18: ...80 92 92 177 347 432 517 10 20 177 D0000070858 HSBB 200 S GB b01 Entry electrical cables c01 Cold water inlet Male thread G 1 c06 DHW outlet Diameter mm 22 c10 DHW circulation Male thread G 1 2 c12 Sa...

Page 19: ...m tundish with continuous fall 11 Equipotential bond 12 Drain valve 13 Cylinder 14 DHW outlet 15 T P valve 16 Metal discharge pipe D1 from T P valve to tundish 17 Expansion vessel 18 Expansion relief...

Page 20: ...heating circuit BT01 Temperature sensor heat pump flow BT02 Temperature sensor heat pump return BT06 Temperature sensor heat pump buffer cylinder not for HSBB or TSBB eco BT20 Temperature sensor DHW...

Page 21: ...X1 7 Connector heating circuit temperature sensor 3 AA01 X1 8 Connector DHW cylinder sensor BT20 AA01 X1 9 Connector source sensor AA01 X1 10 Connector heat source 2 AA01 X1 11 Connector flow cooling...

Page 22: ...l min 22 6 Max operating temperature heating water C 89 Application limits Max permissible pressure Design Pressure DHW cylinder MPa 0 7 Test pressure DHW cylinder MPa 1 5 Max permissible pressure Des...

Page 23: ...cordance with national regulations HSBB 200 S GB set Values Expansion vessel volume l 12 Expansion vessel pre charge pressure MPa 0 15 Nominal design flow rate of heating system at A 7 W35 and 7 K m h...

Page 24: ...land STIEBEL ELTRON OY Kapinakuja 1 04600 M nts l Tel 020 720 9988 info stiebel eltron fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz C dex 3 Tel 0387 743...

Reviews: