iNSTallaTiON
Decommissioning
16
| HSBB 200 S (GB) www.stiebel-eltron.com
13.2 Commissioning the heat pump manager
Commission the heat pump manager and make all settings in
accordance with the operating and installation instructions for
the heat pump manager.
Note
For DHW mode, ensure that the PARALLEL OPERATION
option is set in the heat pump manager. With this setting,
the cylinder charging pump / heating circuit pump is also
activated in DHW mode.
To set the heat pump manager:
f
f
With the MENU key, call up the main menu.
f
f
Select the menu or value and confirm with OK:
SETTINGS
Value
DHW
STANDARD SETTING
DHW MODE
PARALLEL OPERATION
Note
On appliances with a single phase connection, set the
heat pump manager as follows for calculating the amount
of heat.
To set the heat pump manager:
f
f
With the MENU key, call up the main menu.
f
f
Select the menu or value and confirm with OK:
SETTINGS
Value
HEATING
ELECTRIC REHEATING
NUMBER OF STAGES
2
Area cooling setting
!
Material losses
Condensation caused by the temperature falling below
the dew point can lead to material losses. HSBB is there-
fore exclusively approved for area cooling.
Adjusting the heat pump manager settings for area cooling:
f
f
With the MENU key, call up the main menu.
f
f
Select the menu or value and confirm with OK:
SETTINGS
Value
COOLING
COOLING
ON
STANDARD SETTING
COOLING CAPACITY
system specific
ACTIVE COOLING
AREA COOLING
ON
SET FLOW TEMPERATURE
system specific
FLOW TEMP HYSTERESIS
system specific
SET ROOM TEMPERATURE
system specific
13.3 Appliance handover
f
f
Explain the appliance function to users and familiarise them
with its operation.
f
f
Make users aware of potential dangers.
f
f
Hand over these instructions.
14. Decommissioning
!
Material losses
Observe the temperature application limits and the min-
imum circulation volume of the heat pump.
!
Material losses
Drain the system when there is a risk of frost and the heat
pump is completely switched off (see chapter "Mainte-
nance / Draining the DHW cylinder").
f
f
If you take the system out of use, set the heat pump manager
to standby so that the safety functions that protect the appli-
ance (e.g. frost protection) remain active.